2019-02-26 06:51:07****CORRECTIONS****
  
 SAMANTHA HILL
 561 805 6724
 [email protected]
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 SEE PREVIOUS LIST. NO NEW DOCUMENTS WERE SUBMITTED FOR
 THIS REVIEW.
  
 FBC 107. PLEASE PROVIDE MORE INFORMATION:
  
 1. THE INFORMATION PROVIDED ON THE SCHEDULE FOR
 INSTALLATION OF OPENING PROTECTIVE DEVICES, SHOWS THE
 SHUTTERS IN A HORIZONTAL SPAN, THIS SHOULD BE IN A
 VERTICAL AS PER THE IDENTIFIED DETAILS IN THE PRODUCT
 APPROVAL.
 2. USING THE ALTERNATE 8 ANCHORS NEEDS TO HAVE A
 GREATER EDGE DISTANCE THAN USING THE TAPCONS. THERE MAY
 NOT BE ENOUGH WOOD SUBSTRATE TO MEET THE EDGE DISTANCE
 REQUIREMENTS, CONSIDERING THE WOOD FRAMED EXISTING
 CONDITION.
  
 PLEASE REVIEW THE SUBMITTED INFORMATION AND RE-SUBMIT
 CLARIFYING THE ORIENTATION AND ANCHORING OF THE PANELS
 AT OPENING #1.
  
 NEW COMMENT:
  
 2. SEVERAL DOCUMENTS WERE SUBMITTED MULTIPLE TIMES. FOR
 EXAMPLE; DESIGN PRESSURE PAGE WAS UPLOADED TWICE, FLOOR
 PLAN TWICE, TWO DIFFERENT FILES FOR THE INSTALLATION
 SCHEDULE. PLEASE REFER TO THE PROJECTDOX NAMING
 CONVENTION OR, IN THE FUTURE, SUBMIT PAPER RATHER THAN
 DIGITAL.
  