2019-02-26 06:51:07 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | 561 805 6724 | | [email protected] | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | SEE PREVIOUS LIST. NO NEW DOCUMENTS WERE SUBMITTED FOR | | THIS REVIEW. | | | | FBC 107. PLEASE PROVIDE MORE INFORMATION: | | | | 1. THE INFORMATION PROVIDED ON THE SCHEDULE FOR | | INSTALLATION OF OPENING PROTECTIVE DEVICES, SHOWS THE | | SHUTTERS IN A HORIZONTAL SPAN, THIS SHOULD BE IN A | | VERTICAL AS PER THE IDENTIFIED DETAILS IN THE PRODUCT | | APPROVAL. | | 2. USING THE ALTERNATE 8 ANCHORS NEEDS TO HAVE A | | GREATER EDGE DISTANCE THAN USING THE TAPCONS. THERE MAY | | NOT BE ENOUGH WOOD SUBSTRATE TO MEET THE EDGE DISTANCE | | REQUIREMENTS, CONSIDERING THE WOOD FRAMED EXISTING | | CONDITION. | | | | PLEASE REVIEW THE SUBMITTED INFORMATION AND RE-SUBMIT | | CLARIFYING THE ORIENTATION AND ANCHORING OF THE PANELS | | AT OPENING #1. | | | | NEW COMMENT: | | | | 2. SEVERAL DOCUMENTS WERE SUBMITTED MULTIPLE TIMES. FOR | | EXAMPLE; DESIGN PRESSURE PAGE WAS UPLOADED TWICE, FLOOR | | PLAN TWICE, TWO DIFFERENT FILES FOR THE INSTALLATION | | SCHEDULE. PLEASE REFER TO THE PROJECTDOX NAMING | | CONVENTION OR, IN THE FUTURE, SUBMIT PAPER RATHER THAN | | DIGITAL. | | |
|