Plan Review Notes
Plan Review Notes For Permit 18080655
Permit Number 18080655
Review Stop B
Sequence Number 3
Notes
Date Text
2018-12-17 17:03:47****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 FBC 107. PLEASE PROVIDE MORE INFORMATION:
  
 1. THE INFORMATION PROVIDED ON THE SCHEDULE FOR
 INSTALLATION OF OPENING PROTECTIVE DEVICES, SHOWS THE
 SHUTTERS IN A HORIZONTAL SPAN, THIS SHOULD BE IN A
 VERTICAL AS PER THE IDENTIFIED DETAILS IN THE PRODUCT
 APPROVAL.
 2. USING THE ALTERNATE 8 ANCHORS NEEDS TO HAVE A
 GREATER EDGE DISTANCE THAN USING THE TAPCONS. THERE MAY
 NOT BE ENOUGH WOOD SUBSTRATE TO MEET THE EDGE DISTANCE
 REQUIREMENTS, CONSIDERING THE WOOD FRAMED EXISTING
 CONDITION.
  
 PLEASE REVIEW THE SUBMITTED INFORMATION AND RE-SUBMIT
 CLARIFYING THE ORIENTATION AND ANCHORING OF THE PANELS
 AT OPENING #1.