Plan Review Notes For Permit 18080655 |
Permit Number |
18080655 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2018-12-17 17:03:47 | ****CORRECTIONS**** | | | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | FBC 107. PLEASE PROVIDE MORE INFORMATION: | | | | 1. THE INFORMATION PROVIDED ON THE SCHEDULE FOR | | INSTALLATION OF OPENING PROTECTIVE DEVICES, SHOWS THE | | SHUTTERS IN A HORIZONTAL SPAN, THIS SHOULD BE IN A | | VERTICAL AS PER THE IDENTIFIED DETAILS IN THE PRODUCT | | APPROVAL. | | 2. USING THE ALTERNATE 8 ANCHORS NEEDS TO HAVE A | | GREATER EDGE DISTANCE THAN USING THE TAPCONS. THERE MAY | | NOT BE ENOUGH WOOD SUBSTRATE TO MEET THE EDGE DISTANCE | | REQUIREMENTS, CONSIDERING THE WOOD FRAMED EXISTING | | CONDITION. | | | | PLEASE REVIEW THE SUBMITTED INFORMATION AND RE-SUBMIT | | CLARIFYING THE ORIENTATION AND ANCHORING OF THE PANELS | | AT OPENING #1. |
|