2018-10-19 16:54:33****CORRECTIONS****
 W.P.B. PERMIT: 18080655
 2 ND REVIEW: OCTOBER 19, 2018
  
 IS OPENING NUMBER 1 REALLY BEING INSTALLED
 HORIZONTALLY?
 THAT WOULD MEAN THAT THE PANEL IS 15' LONG.
 THE PRODUCT APPROVAL DOESN'T ACCOMODATE PANELS THAT
 SIZE.
  
 TO CLEAR THIS UP ARE YOUR PANELMATES BEING INSTALLED ON
 THE SIDES, OR ON THE TOP AND BOTTOM OF OPENINGS?
 THE SPAN IS EQUIVELANT TO THE LENTH OF PANEL.
  
 IF THE PANELS FOR OPENING 1 ARE INSTALLED WITH
 PANELMATES TOP AND BOTTOM THAN THE PANELS ARE BEING
 INSTALLED VERTICAL AND THE SPAN IS DISTANCE BETWEEN
 ANCHORS.
 SPECIFY THE ALTERNATIVE ANCHOR BEING USED FOR WOOD
 CONNECTION. IF IT IS ALTERNATIVE 8 THAN SEE HOW TOP
 REQUIRES MINIMUM 2" EDGE DISTANCE AND EQUAL SPACING ON
 BOTTOM PLATE.
  
 PLEASE CALL IF ANY QUESTIONS BEFORE RE-SUBMITTING.
 I WILL GO OVER THE DETAILS OF PRODUCT APPROVAL WITH YOU
 BY PHONE, OR COME INTO BUILDING DEPARTMENT FOR CONSULT.
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718