2018-09-05 18:07:58****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. REVISE PLAN TO SHOW MEANS OF ESCAPE REQUIRED BY FBC
 R 310.4; INCLUDE ROOM DESIGNATION.
  
 2. SEE THE INSTALLATION SCHEDULE; IT IS NOT CLEAR HOW
 SPANS WERE DETERMINED. FOR INSTANCE, OPENING 1, W X H,
 183 X 57, SPAN IS 93 BUT SHOULD BE 185.5" (FOR
 HORIZONTAL INSTALLATION, ANCHOR TO ANCHOR WHICH WOULD
 BE WIDTH + EDGE DISTANCE ON EACH SIDE).
  
 SEE ALSO OPENING 5, 33 X 32, SPAN IS 31.5.
  
 THESE ARE TWO EXAMPLES BUT THERE ARE OTHER ERRORS,
 PLEASE REVISE.
  
  