Plan Review Notes For Permit 18080655 |
Permit Number |
18080655 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-09-05 18:07:58 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. REVISE PLAN TO SHOW MEANS OF ESCAPE REQUIRED BY FBC | | R 310.4; INCLUDE ROOM DESIGNATION. | | | | 2. SEE THE INSTALLATION SCHEDULE; IT IS NOT CLEAR HOW | | SPANS WERE DETERMINED. FOR INSTANCE, OPENING 1, W X H, | | 183 X 57, SPAN IS 93 BUT SHOULD BE 185.5" (FOR | | HORIZONTAL INSTALLATION, ANCHOR TO ANCHOR WHICH WOULD | | BE WIDTH + EDGE DISTANCE ON EACH SIDE). | | | | SEE ALSO OPENING 5, 33 X 32, SPAN IS 31.5. | | | | THESE ARE TWO EXAMPLES BUT THERE ARE OTHER ERRORS, | | PLEASE REVISE. | | | | |
|