Plan Review Notes
Plan Review Notes For Permit 18080642
Permit Number 18080642
Review Stop M
Sequence Number 1
Notes
Date Text
2018-08-24 17:04:461ST REVIEW FBC-2014 MECHANICAL
 PERMIT #17100726
 REVISION #18080642
 8/24/18
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) RETURN TRANSFER DUCTS SHALL BE SIZED 1-1/2 TIMES THE
 CROSS-SECTIONAL ARE OF THE SUPPLY DUCT ENTERING THE
 ROOM OR SPACE IT IS SERVING- SECTION M1602.4 (1)
 RESIDENTIAL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  