Plan Review Notes
Plan Review Notes For Permit 18080628
Permit Number 18080628
Review Stop B
Sequence Number 1
Notes
Date Text
2018-08-14 14:00:00PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE SHORING/RESHORING PLANS ARE REQUIRED TO BE
 SIGNED AND SEALED BY THE ENGINEER. THE PLANS THAT WERE
 SUBMITTED HAVE A DIGITAL SIGNATURE WHICH IS ONLY
 ACCEPTABLE FOR ELECTRONICALLY SUBMITTED PLANS.
 61G15-23.003 PROCEDURES FOR PHYSICALLY SIGNING AND
 SEALING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS. ENGINEERING PLANS, SPECIFICATIONS, REPORTS
 OR OTHER DOCUMENTS WHICH MUST BE SIGNED, DATED AND
 SEALED IN ACCORDANCE WITH THE PROVISIONS OF SECTION
 471.025, F.S., AND RULE 61G15-23.001, F.A.C. MUST BE
 PHYSICALLY SIGNED, DATED AND SEALED AS PROVIDED HEREIN
 BY THE PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE?S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE?S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
 2) PROVISO ITEM: PROVIDE THE RESUME AND LICENSE
 INFORMATION FOR THE ENGINEER THAT WILL INSPECT THE
 SHORING AND RESHORING TO THE FIELD INSPECTOR.
 FBC110.8.2
  