2018-08-30 17:38:39 | 08/30/2018 1ST PLUMBING/POOL REVIEW **DENIED** WITH |
| COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS |
| SPECIFIC TO THE PUMP BEING INSTALLED ON THIS POOL. THIS |
| IS NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE |
| TDH CALCULATIONS. WPB AMENDMENTS TO THE FBC SEC. |
| 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. |
| 2. SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE MAIN |
| DRAIN AND THE PUMP. WPB AMENDMENTS TO FBC SEC. 107.2.1. |
| 3. BACKFLOW PREVENTER REQUIRED PER THE CITY OF WEST |
| PALM BEACH ORD #2853-95. A PERMIT REQUIRED BY A |
| LICENSED CONTRACTOR AND MUST BE CERTIFIED BY UTILITIES |
| PRIOR TO FINAL INSPECTION. A DUAL CHECK VALVE MAY BE |
| USED IF NO POOL FILL IS INSTALLED AT THE METER AND |
| INSTALLED BY UTILITIES WHICH DOES NOT REQUIRE A PERMIT |
| SO PLEASE CONTACT CITY OF WPB UTILITIES AT 561-822-2240 |
| FOR FURTHER DIRECTIONS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |