Plan Review Notes For Permit 18080583 |
Permit Number |
18080583 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2018-10-02 18:42:28 | BUILDING PROVISO | | PRIOR TO STARTING THE FOUNDATION WORK. PROVIDE THE | | FOLLOWING. | | 1) SUBMIT VIBRO REPLACEMENT PLANS, DRAWINGS AND | | SPECIFICATIONS THAT HAVE BEEN PREPARED BY A SPECIALTY | | ENGINEER AND REVIEWED AND APPROVED IN WRITING BY THE | | DESIGNER OF RECORD FOR THE PROJECT. FBC (CITY | | AMENDMENTS) 107.2.1.2 | | 2) SUBMIT A SIGNED AND SEALED VIBRO REPLACEMENT | | COMPACTION TEST REPORT THAT SHOWS THE ALLOWABLE BEARING | | PRESSURE OF 8,000 PSF REQUIRED FOR THE FOUNDATION | | DESIGN HAS BEEN ACHIEVED. |
|