Plan Review Notes For Permit 18080583 |
Permit Number |
18080583 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-09-28 09:09:47 | PROVISO: | | 1. PROVIDE A SANITARY ISOMETRIC DRAWING THAT SHOWS ONLY | | THE UNDERGROUND PIPING AND EXPAND IT LARGE ENOUGH SO | | THAT NONE OF THE PIPES OVERLAP AND SHOW SIZING, DFU | | LOAD AND THE PITCH THE PIPE WILL BE INSTALLED. PER WPB | | AMEND TO FBC 107.3.5.1.3(13) | | 2. PROVIDE A STORM DRAIN ISOMETRIC DRAWING THAT SHOWS | | ONLY THE UNDERGROUND PIPING AND EXPAND IT LARGE ENOUGH | | SO THAT NONE OF THE PIPES OVERLAP AND SHOW SIZING. . | | PER WPB AMEND TO FBC 107.3.5.1.3(13) | | 3. PROVIDE A SANITARY FLOOR PLAN. PER WPB AMEND TO FBC | | 107.2.1 | | 4. PROVIDE A SEPARATE STORM DRAIN FLOOR PLAN. PER WPB | | AMEND TO FBC 107.2.1 | | 5. SHALL COMPLY WITH PROVISO PRIOR TO PLUMBING PERMIT | | BEING ISSUED. | | | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561-805-6711 | | [email protected] | | |
|