Plan Review Notes
Plan Review Notes For Permit 18080583
Permit Number 18080583
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2018-08-23 12:47:17THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) SHEET G 001 - THERE ARE INCORRECT REFERNCES, 2010
 AND 2012, TO THE CURRENT EDITION OF THE FIRE CODE
  
 THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE
 6TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING
 THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER
 APPLICABLE CODES OR STANDARDS.
  
 FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 13, 2013 EDITION.
 STANDPIPE WORK SHALL COMPLY WITH NFPA 14, STANDARD FOR
 THE INSTALLATION OF STANDPIPE AND HOSE SYSTEMS, 2013
 EDITION.
 FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 72, 2013 EDITION.
 CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF
 NFPA 241, 2013 EDITION.
 FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS
 OF NFPA 10, 2013 EDITION.
 ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION.
 CLEAN AGENT SYSTEMS SHALL COMPLY WITH NFPA 2001, 2012
 EDITION.
 EMERGENCY AND STANDBY POWER SYSTEMS SHALL COMPLY WITH
 NFPA 110, 2013 EDITION.
 COMMERCIAL COOKING SHALL COMPLY WITH NFPA 96, 2014
 EDITION.
 SMOKE CONTRO SHALL COMPLY WITH NFPA 92, STANDARD FOR
 SMOKE CONTROL SYSTEMS, 2012 EDITION.
 COMPRESSED GAS SHLL COMPLY WITH NFPA 55, COMPRESSED
 GASES AND CRYOGENIC FLUIDS CODE, 2013 EDITION.
 PARKING GARAGES SHALL COMLY WITH NFPA 88A, STANDARD FOR
 PARKING STRUCTURES, 2015 EDITION.
 HEALTHCARE FACILITIES SHALL COMPLY WITH NFPA 99, HEALTH
 CARE FACILITIES CODE, 2015 EDITION.
  
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY WITH A DETAILED
 NARRATIVE.
  
  
  
  
 2) ALL SHEET - THERE IS NO INDICATIONS OF ANY FIRE LINE
 WORK OR FIRE PUMP ROOM.
  
 THERE MAY BE REQUIRED FIRE LINE WORK WITHIN THE SCOPE
 OF THE FOUNDATION.
  
 PLEASE REVIEW AND CORRECT OR JUSTIFY OMISSION OF SUCH
 WORK WITH A DETAILED NARRATIVE.
  
  
  
 3) SHEET P 200 - THERE IS NO INDICATION OF A DRAIN
 WITHIN A FIRE PUMP ROOM.
  
 PER NFPA 20, NFPA 20, STANDARD FOR THE INSTALLATION OF
 STATIONARY PUMPS
 FOR FIRE PROTECTION, 2013 EDITION.
  
 4.12.7* DRAINAGE.
 4.12.7.1 FLOORS SHALL BE PITCHED FOR ADEQUATE DRAINAGE
 OF ESCAPING
 WATER AWAY FROM CRITICAL EQUIPMENT SUCH AS THE PUMP,
 DRIVER, CONTROLLER, AND SO FORTH.
 4.12.7.2 THE PUMP ROOM OR PUMP HOUSE SHALL BE PROVIDED
 WITH A FLOOR DRAIN THAT WILL DISCHARGE TO A FROST-FREE
 LOCATION.
  
  
 DOES THIS PROJECT PROPOSE A FIRE PUMP TO SUPPORT THE
 REQUIRED FIRE SPRINKLER SYSTEM?
  
 PLEASE PROVIDE INDICATIONS OF A FLOOR DRAIN IN THE FIRE
 PUMP ROOM OR JUSTIFY WITH SPECIFIC DETAIL AND CODE
 REFERENCES.
  
  
  
  
 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL