2018-08-23 12:47:17 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| |
| 1) SHEET G 001 - THERE ARE INCORRECT REFERNCES, 2010 |
| AND 2012, TO THE CURRENT EDITION OF THE FIRE CODE |
| |
| THE PROPOSED PROJECT SHALL MEET THE REQUIREMENTS OF THE |
| 6TH EDITION OF FLORIDA FIRE PREVENTION CODE INCLUDING |
| THE 2015 EDITION OF NFPA 1 AND NFPA 101 AND ALL OTHER |
| APPLICABLE CODES OR STANDARDS. |
| |
| FIRE SPRINKLER WORK SHALL COMPLY WITH THE REQUIREMENTS |
| OF NFPA 13, 2013 EDITION. |
| STANDPIPE WORK SHALL COMPLY WITH NFPA 14, STANDARD FOR |
| THE INSTALLATION OF STANDPIPE AND HOSE SYSTEMS, 2013 |
| EDITION. |
| FIRE ALARM WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| NFPA 72, 2013 EDITION. |
| CONSTRUCTION WORK SHALL COMPLY WITH THE REQUIREMENTS OF |
| NFPA 241, 2013 EDITION. |
| FIRE EXTINGUISHERS SHALL COMPLY WITH THE REQUIREMENTS |
| OF NFPA 10, 2013 EDITION. |
| ELECTRIC WORK SHALL COMPLY WITH NFPA 70, 2014 EDITION. |
| CLEAN AGENT SYSTEMS SHALL COMPLY WITH NFPA 2001, 2012 |
| EDITION. |
| EMERGENCY AND STANDBY POWER SYSTEMS SHALL COMPLY WITH |
| NFPA 110, 2013 EDITION. |
| COMMERCIAL COOKING SHALL COMPLY WITH NFPA 96, 2014 |
| EDITION. |
| SMOKE CONTRO SHALL COMPLY WITH NFPA 92, STANDARD FOR |
| SMOKE CONTROL SYSTEMS, 2012 EDITION. |
| COMPRESSED GAS SHLL COMPLY WITH NFPA 55, COMPRESSED |
| GASES AND CRYOGENIC FLUIDS CODE, 2013 EDITION. |
| PARKING GARAGES SHALL COMLY WITH NFPA 88A, STANDARD FOR |
| PARKING STRUCTURES, 2015 EDITION. |
| HEALTHCARE FACILITIES SHALL COMPLY WITH NFPA 99, HEALTH |
| CARE FACILITIES CODE, 2015 EDITION. |
| |
| |
| PLEASE REVIEW AND CORRECT OR JUSTIFY WITH A DETAILED |
| NARRATIVE. |
| |
| |
| |
| |
| 2) ALL SHEET - THERE IS NO INDICATIONS OF ANY FIRE LINE |
| WORK OR FIRE PUMP ROOM. |
| |
| THERE MAY BE REQUIRED FIRE LINE WORK WITHIN THE SCOPE |
| OF THE FOUNDATION. |
| |
| PLEASE REVIEW AND CORRECT OR JUSTIFY OMISSION OF SUCH |
| WORK WITH A DETAILED NARRATIVE. |
| |
| |
| |
| 3) SHEET P 200 - THERE IS NO INDICATION OF A DRAIN |
| WITHIN A FIRE PUMP ROOM. |
| |
| PER NFPA 20, NFPA 20, STANDARD FOR THE INSTALLATION OF |
| STATIONARY PUMPS |
| FOR FIRE PROTECTION, 2013 EDITION. |
| |
| 4.12.7* DRAINAGE. |
| 4.12.7.1 FLOORS SHALL BE PITCHED FOR ADEQUATE DRAINAGE |
| OF ESCAPING |
| WATER AWAY FROM CRITICAL EQUIPMENT SUCH AS THE PUMP, |
| DRIVER, CONTROLLER, AND SO FORTH. |
| 4.12.7.2 THE PUMP ROOM OR PUMP HOUSE SHALL BE PROVIDED |
| WITH A FLOOR DRAIN THAT WILL DISCHARGE TO A FROST-FREE |
| LOCATION. |
| |
| |
| DOES THIS PROJECT PROPOSE A FIRE PUMP TO SUPPORT THE |
| REQUIRED FIRE SPRINKLER SYSTEM? |
| |
| PLEASE PROVIDE INDICATIONS OF A FLOOR DRAIN IN THE FIRE |
| PUMP ROOM OR JUSTIFY WITH SPECIFIC DETAIL AND CODE |
| REFERENCES. |
| |
| |
| |
| |
| 4) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 5) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |