2018-09-25 16:40:46PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 THE STORM PANELS ARE NOT CODE COMPLIANT BASED ON THE
 DOCUMENTS THAT WERE SUBMITTED. FBC-R 301.2.1.2
  
 1) FROM THE TABLE FOR WOOD ON SHEET 10 OF THE PRODUCT
 APPROVAL, THE MAXIMUM PANEL LENGTH 6'-0" (72") FOR A
 DESIGN PRESSURE OF MORE THAN -45.8 PSF. YOUR PANEL
 SPANS ARE 90-1/2" AND 106-1/2" PER THE INSTALLATION
 SCHEDULE.
  
 2) THE TABLES ON SHEET 7 FOR CONCRETE AND MASONRY GO UP
 TO A MAXIMUM SPAN OF 7'-4" (88") FOR DESIGN PRESSURES
 OF MORE THAN -45.8 PSF. YOUR PANEL SPANS ARE 90-1/2"
 AND 106-1/2" PER THE INSTALLATION SCHEDULE.
  
 3) THE EDGE DISTANCE FOR CONCRETE AND MASONRY
 INSTALLATIONS IS REQUIRED TO BE 3-1/2" TO USE THE
 ANCHOR SPACING IN THE TABLES ON SHEET 7.
  