Plan Review Notes
Plan Review Notes For Permit 18080486
Permit Number 18080486
Review Stop P
Sequence Number 2
Notes
Date Text
2018-10-18 15:11:56PLUMBING COMMENTS: APPROVED
  
 PROVISO
 1. PROVIDE THERMAL EXPANSION DEVICE IN COLD WATER
 SUPPLY TO WATER HEATER. FBC PL 607.3
 2. WATER HEATER IS BOTTOM FED. PROVIDE VACUUM RELIEF
 VALVE IN COLD WATER SUPPLY TO WATER HEATER. FPC PL
 504.2
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715