Plan Review Notes For Permit 18080466 |
Permit Number |
18080466 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-09-26 14:56:37 | ****CORRECTIONS**** | | W.P.B. PERMIT: 18080466 | | REVIEWED: SEPTEMBER 26, 2018 | | | | DYLAN BATTLES | | BUILDING PLANS EXAMINER I | | [email protected] | | 561-805-6718 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC R = FBC RESIDENTIAL | | | | [FBC AMENDED 107.2.1.2]ADDITIONAL INFO ON PRODUCT | | APPROVALS NEEDED FOR ROOFING, OR INDICATE THAT YOU | | WOULD TO DEFER IT UNTIL SUB-PERMIT APPLICATION. | | -SELECT WHICH SYSYTEM IS BEING USED BASED ON MDP. | | -PROVIDE ENGINEERING (RAS 117) FOR ENHANCED NAILING AS | | STATED IN PRODUCT APPROVAL UNDER GENERAL LIMITATIONS | | #7. | | -WHAT IS THE EXISTING ROOF PITCH, AND THE NEW ROOF TO | | BE SHINGLED? | | [FBC R905.2.2] [FBC R905.1.1]FOR ROOF SLOPES FROM TWO | | UNITS VERTICAL IN 12 UNITS HORIZONTAL (2:12) AND LESS | | THAN FOUR UNITS VERTICAL IN 12 UNITS HORIZONTAL (4:12), | | DOUBLE UNDERLAYMENT APPLICATION IS REQUIRED. | | |
|