2018-09-18 11:49:36 | 1ST REVIEW: FBC 2017 6TH EDITION |
| PERMIT 18080466 |
| PLUMBING COMMENTS: DENIED |
| |
| 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS |
| IS FOR TOTAL PROJECT, NOT JUST PLUMBING. FBC 109.3 |
| 2. TANKLESS WATER HEATER: 1ST REVIEW: FBC 2017 6TH |
| EDITION |
| PERMIT 18080466 |
| PLUMBING COMMENTS: DENIED |
| |
| 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS |
| IS FOR TOTAL PROJECT, NOT JUST PLUMBING. FBC 109.3 |
| 2. TANKLESS WATER HEATER: PROVIDE ON PLUMBING PLAN THE |
| MANUFACTURER, MODEL AND SPECS FOR TANKLESS WATER |
| HEATER. CONFIRM THAT MANUFACTURER HAS NOT DESIGNATED |
| THIS UNIT AS A POINT OF USE UNIT DESIGNED FOR USE WITH |
| SINGLE FIXTURE AND THAT IT WILL PROVIDE ADEQUATE HOT |
| WATER FOR THE MASTER BATH FIXTURES IN ACCORDANCE WITH |
| FBC RES 2903.1 |
| 3. PROVIDE NOTE: SHOWER CONTROL VALVE(S) SHALL BE |
| PRESSURE BALANCED PB,THERMOSTATIC MIXING (TM) OR |
| COMBINATION PB/TM VALVE TYPES WITH HIGH TEMPERATURE |
| LIMITING STOP. 2017 FBC RES 2708.4 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |