2019-03-15 16:49:57 | 4TH REVIEW FBC-2017 MECHANICAL |
| PERMIT #18080413 |
| 2/4/19 |
| |
| CODES IN EFFECT: |
| |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| COMMENT #3 FROM THE 3RD REVIEW PRINTED BELOW HAS NOT |
| BEEN ADDRESSED. I HAVE PRINTED THE CODE SECTION BELOW. |
| PLEASE FORWARD TO THE ARCHITECT OF RECORD. |
| PLEASE NOTE THAT UNTIL ADEQUATE INFORMATION IS PROVIDED |
| TO VERIFY COMPLIANCE WITH THE EXCEPTION, A HAZARDOUS |
| EXHAUST SYSTEM WILL BE REQUIRED, AND DAMPERS ARE |
| PROHIBITED IN THE EXHAUST DUCT- SECTION 510.7.1 FBC M. |
| SEE SECTIONS 510.7.3 FOR DUCT ENCLOSURE REQUIREMENT, |
| AND 510.9 FOR DUCT MATERIALS |
| |
| 3) M1.1: REFER TO SECTION 510.2 EXCEPTION FBC M AND |
| VERIFY COMPLIANCE OR A HAZARDOUS EXHAUST SYSTEM |
| COMPLYING WITH SECTIONS 510.6- 510.10 SHALL BE |
| PROVIDED. THE CURRENT EXHAUST SYSTEM SHOWN IS NOT IN |
| COMPLIANCE. |
| |
| 510.2 WHERE REQUIRED. |
| |
| A HAZARDOUS EXHAUST SYSTEM SHALL BE REQUIRED WHEREVER |
| OPERATIONS INVOLVING THE HANDLING OR PROCESSING OF |
| HAZARDOUS MATERIALS, IN THE ABSENCE OF SUCH EXHAUST |
| SYSTEMS AND UNDER NORMAL OPERATING CONDITIONS, HAVE THE |
| POTENTIAL TO CREATE ONE OF THE FOLLOWING CONDITIONS: |
| |
| 1.A FLAMMABLE VAPOR, GAS, FUME, MIST OR DUST IS PRESENT |
| IN CONCENTRATIONS EXCEEDING 25 PERCENT OF THE LOWER |
| FLAMMABILITY LIMIT OF THE SUBSTANCE FOR THE EXPECTED |
| ROOM TEMPERATURE. |
| |
| 2.A VAPOR, GAS, FUME, MIST OR DUST WITH A HEALTH-HAZARD |
| RATING OF 4 IS PRESENT IN ANY CONCENTRATION. |
| |
| 3.A VAPOR, GAS, FUME, MIST OR DUST WITH A HEALTH-HAZARD |
| RATING OF 1, 2 OR 3 IS PRESENT IN CONCENTRATIONS |
| EXCEEDING 1 PERCENT OF THE MEDIAN LETHAL CONCENTRATION |
| OF THE SUBSTANCE FOR ACUTE INHALATION TOXICITY. |
| |
| EXCEPTION: LABORATORIES, AS DEFINED IN SECTION 510.1, |
| EXCEPT WHERE THE CONCENTRATIONS LISTED IN ITEM 1 ARE |
| EXCEEDED OR A VAPOR, GAS, FUME, MIST OR DUST WITH A |
| HEALTH-HAZARD RATING OF 1, 2, 3 OR 4 IS PRESENT IN |
| CONCENTRATIONS EXCEEDING 1 PERCENT OF THE MEDIAN LETHAL |
| CONCENTRATION OF THE SUBSTANCE FOR ACUTE INHALATION |
| TOXICITY. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |