Plan Review Notes
Plan Review Notes For Permit 18080413
Permit Number 18080413
Review Stop M
Sequence Number 4
Notes
Date Text
2019-03-15 16:49:574TH REVIEW FBC-2017 MECHANICAL
 PERMIT #18080413
 2/4/19
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 COMMENT #3 FROM THE 3RD REVIEW PRINTED BELOW HAS NOT
 BEEN ADDRESSED. I HAVE PRINTED THE CODE SECTION BELOW.
 PLEASE FORWARD TO THE ARCHITECT OF RECORD.
 PLEASE NOTE THAT UNTIL ADEQUATE INFORMATION IS PROVIDED
 TO VERIFY COMPLIANCE WITH THE EXCEPTION, A HAZARDOUS
 EXHAUST SYSTEM WILL BE REQUIRED, AND DAMPERS ARE
 PROHIBITED IN THE EXHAUST DUCT- SECTION 510.7.1 FBC M.
 SEE SECTIONS 510.7.3 FOR DUCT ENCLOSURE REQUIREMENT,
 AND 510.9 FOR DUCT MATERIALS
  
 3) M1.1: REFER TO SECTION 510.2 EXCEPTION FBC M AND
 VERIFY COMPLIANCE OR A HAZARDOUS EXHAUST SYSTEM
 COMPLYING WITH SECTIONS 510.6- 510.10 SHALL BE
 PROVIDED. THE CURRENT EXHAUST SYSTEM SHOWN IS NOT IN
 COMPLIANCE.
  
 510.2 WHERE REQUIRED.
  
 A HAZARDOUS EXHAUST SYSTEM SHALL BE REQUIRED WHEREVER
 OPERATIONS INVOLVING THE HANDLING OR PROCESSING OF
 HAZARDOUS MATERIALS, IN THE ABSENCE OF SUCH EXHAUST
 SYSTEMS AND UNDER NORMAL OPERATING CONDITIONS, HAVE THE
 POTENTIAL TO CREATE ONE OF THE FOLLOWING CONDITIONS:
  
 1.A FLAMMABLE VAPOR, GAS, FUME, MIST OR DUST IS PRESENT
 IN CONCENTRATIONS EXCEEDING 25 PERCENT OF THE LOWER
 FLAMMABILITY LIMIT OF THE SUBSTANCE FOR THE EXPECTED
 ROOM TEMPERATURE.
  
 2.A VAPOR, GAS, FUME, MIST OR DUST WITH A HEALTH-HAZARD
 RATING OF 4 IS PRESENT IN ANY CONCENTRATION.
  
 3.A VAPOR, GAS, FUME, MIST OR DUST WITH A HEALTH-HAZARD
 RATING OF 1, 2 OR 3 IS PRESENT IN CONCENTRATIONS
 EXCEEDING 1 PERCENT OF THE MEDIAN LETHAL CONCENTRATION
 OF THE SUBSTANCE FOR ACUTE INHALATION TOXICITY.
  
 EXCEPTION: LABORATORIES, AS DEFINED IN SECTION 510.1,
 EXCEPT WHERE THE CONCENTRATIONS LISTED IN ITEM 1 ARE
 EXCEEDED OR A VAPOR, GAS, FUME, MIST OR DUST WITH A
 HEALTH-HAZARD RATING OF 1, 2, 3 OR 4 IS PRESENT IN
 CONCENTRATIONS EXCEEDING 1 PERCENT OF THE MEDIAN LETHAL
 CONCENTRATION OF THE SUBSTANCE FOR ACUTE INHALATION
 TOXICITY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER