2019-02-04 11:07:16 | 3RD REVIEW FBC-2017 MECHANICAL |
| PERMIT #18080413 |
| 2/4/19 |
| |
| CODES IN EFFECT: |
| |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M0.2: BASED ON THE SUBMITTED MSDS SHEETS, |
| STORAGE OF FLAMMABLE LIQUIDS NOT EXCEEDING THE MAXIMUM |
| ALLOWABLE QUANTITIES WILL OCCUR IN THE LAB WHICH |
| REQUIRES THE ROOM TO BE DESIGNATED AS A "CONTROL AREA" |
| - SEE SECTIONS 202 AND 414.2 FBC. THE CONTROL AREA |
| (LAB) IS REQUIRED TO BE SEPARATED FROM OTHER ROOMS AND |
| SPACES WITH 1-HR FIRE-RESISTANT RATED CONSTRUCTION- |
| SECTION 414.2.4 AND TABLE 414.2.2 FBC B. |
| |
| 2) M1.1: BECAUSE FIRE-BARRIERS ARE NOW REQUIRED TO |
| ENCLOSE THE LAB, ALL DUCT PENETRATIONS SHALL BE |
| PROTECTED WITH FIRE DAMPERS- SECTION 607.5.2 FBC M. |
| |
| 3) M1.1: REFER TO SECTION 510.2 EXCEPTION FBC M AND |
| VERIFY COMPLIANCE OR A HAZARDOUS EXHAUST SYSTEM |
| COMPLYING WITH SECTIONS 510.6- 510.10 SHALL BE |
| PROVIDED. THE CURRENT EXHAUST SYSTEM SHOWN IS NOT IN |
| COMPLIANCE. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |