Plan Review Notes
Plan Review Notes For Permit 18080413
Permit Number 18080413
Review Stop M
Sequence Number 3
Notes
Date Text
2019-02-04 11:07:163RD REVIEW FBC-2017 MECHANICAL
 PERMIT #18080413
 2/4/19
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M0.2: BASED ON THE SUBMITTED MSDS SHEETS,
 STORAGE OF FLAMMABLE LIQUIDS NOT EXCEEDING THE MAXIMUM
 ALLOWABLE QUANTITIES WILL OCCUR IN THE LAB WHICH
 REQUIRES THE ROOM TO BE DESIGNATED AS A "CONTROL AREA"
 - SEE SECTIONS 202 AND 414.2 FBC. THE CONTROL AREA
 (LAB) IS REQUIRED TO BE SEPARATED FROM OTHER ROOMS AND
 SPACES WITH 1-HR FIRE-RESISTANT RATED CONSTRUCTION-
 SECTION 414.2.4 AND TABLE 414.2.2 FBC B.
  
 2) M1.1: BECAUSE FIRE-BARRIERS ARE NOW REQUIRED TO
 ENCLOSE THE LAB, ALL DUCT PENETRATIONS SHALL BE
 PROTECTED WITH FIRE DAMPERS- SECTION 607.5.2 FBC M.
  
 3) M1.1: REFER TO SECTION 510.2 EXCEPTION FBC M AND
 VERIFY COMPLIANCE OR A HAZARDOUS EXHAUST SYSTEM
 COMPLYING WITH SECTIONS 510.6- 510.10 SHALL BE
 PROVIDED. THE CURRENT EXHAUST SYSTEM SHOWN IS NOT IN
 COMPLIANCE.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  