2018-10-24 15:05:00 | 2ND REVIEW FBC-2017 MECHANICAL |
| PERMIT #18080413 |
| 10/24/18 |
| |
| CODES IN EFFECT: |
| |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) M0.2: A) REFER TO SECTION 414.1.3 FBC B AND PROVIDE |
| THE HAZARDOUS MATERIALS CLASSIFICATIONS FOR ALL |
| CHEMICALS LISTED IN THE SCHEDULE AND SUBMIT MSDS SHEETS |
| FOR EACH- SEE TABLES 307.1(1) AND 307.1(2). B) SHOW THE |
| LOCATION OF THE FUME HOOD ON THE PLAN AND SUBMIT |
| MANUFACTURER'S SPECIFICATIONS- |
| |
| 2) M1.1: RECIRCULATION OF AIR FROM THE LAB IS ONLY |
| PERMITTED WHERE THE RESULTING AIRSTREAM CONSISTS OF NOT |
| MORE THAN 10 PERCENT AIR RECIRCULATED FORM THE ROOM- |
| TABLE 403.3.1.1 FOOTNOTE G. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |