2018-10-24 15:05:002ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18080413
 10/24/18
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) M0.2: A) REFER TO SECTION 414.1.3 FBC B AND PROVIDE
 THE HAZARDOUS MATERIALS CLASSIFICATIONS FOR ALL
 CHEMICALS LISTED IN THE SCHEDULE AND SUBMIT MSDS SHEETS
 FOR EACH- SEE TABLES 307.1(1) AND 307.1(2). B) SHOW THE
 LOCATION OF THE FUME HOOD ON THE PLAN AND SUBMIT
 MANUFACTURER'S SPECIFICATIONS-
  
 2) M1.1: RECIRCULATION OF AIR FROM THE LAB IS ONLY
 PERMITTED WHERE THE RESULTING AIRSTREAM CONSISTS OF NOT
 MORE THAN 10 PERCENT AIR RECIRCULATED FORM THE ROOM-
 TABLE 403.3.1.1 FOOTNOTE G.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  