Plan Review Notes
Plan Review Notes For Permit 18080413
Permit Number 18080413
Review Stop P
Sequence Number 1
Notes
Date Text
2018-08-31 08:59:411ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. PROVIDE THE DIMENSIONS OF THE SHOWER OPENING SHALL
 COMPLY WITH FBC ACC 608.2.3
  
 2. SHOW COMPLIANCE WITH FBC ACC 608.5.3 ALTERNATE
 ROLL-IN TYPE SHOWER COMPARTMENTS.
 IN ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS, THE
 CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT SHALL BE
 LOCATED ABOVE THE GRAB BAR, BUT NO HIGHER THAN 48
 INCHES ABOVE THE SHOWER FLOOR. WHERE A SEAT IS
 PROVIDED, THE CONTROLS, FAUCETS, AND SHOWER SPRAY UNIT
 SHALL BE LOCATED ON THE SIDE WALL ADJACENT TO THE SEAT
 27 INCHES MAXIMUM FROM THE SIDE WALL BEHIND THE SEAT OR
 SHALL BE LOCATED ON THE BACK WALL OPPOSITE THE SEAT 15
 INCHES MAXIMUM, LEFT OR RIGHT, OF THE CENTERLINE OF THE
 SEAT. WHERE A SEAT IS NOT PROVIDED, THE CONTROLS,
 FAUCETS, AND SHOWER SPRAY UNIT SHALL BE INSTALLED ON
 THE SIDE WALL FARTHEST FROM THE COMPARTMENT ENTRY
  
 3. SHOW COMPLIANCE WITH FBC ACC 608.3.3 ALTERNATE
 ROLL-IN TYPE SHOWER COMPARTMENTS.
 IN ALTERNATE ROLL-IN TYPE SHOWER COMPARTMENTS, GRAB
 BARS SHALL BE PROVIDED ON THE BACK WALL AND THE SIDE
 WALL FARTHEST FROM THE COMPARTMENT ENTRY. GRAB BARS
 SHALL NOT BE PROVIDED ABOVE THE SEAT. GRAB BARS SHALL
 BE INSTALLED 6 INCHES MAXIMUM FROM ADJACENT WALLS.
  
 4. THE GRAB BARS SHALL BE MEASURED TO THE TOP OF THE
 GRIPPING SURFACE FROM FINISHED FLOOR. PER FBC ACC 609.4
  
 5. TOILET PAPER DISPENSERS SHALL BE 7 INCHES MINIMUM
 AND 9 INCHES MAXIMUM IN FRONT OF THE WATER CLOSET
 MEASURED TO THE CENTERLINE OF THE DISPENSER. PLEASE
 CLARIFY ON THE PLAN PER FBC ACC 604.7
  
 6. A MINIMUM OF ONE OF THE SINKS IN THE EXAM ROOMS
 SHALL COMPLY WITH FBC ACC 606.2, 606.3 PER FBC ACC
 212.3
  
 7. A LINT TRAP IS REQUIRED FOR THE DISCHARGE OF THE
 WASHING MACHINE IF MACHINE IS A COMMERCIAL MODEL
 PROVIDE MAKE AND MODEL OF EXISTING WASHING MACHINE. PER
 FBC PL 1003.6 EXCEPTIONS(2)
  
 8. PLEASE PROVIDE THE FOLLOWING INFORMATION ON THE PLAN
 PER WPB AMEND TO FBC
 A) THE LEVEL OF ALTERATION.
 B) THE OCCUPANT LOAD.
  
 8. A DRINKING FOUNTAIN MAYBE REQUIRED IF OCCUPANT LOAD
 INCREASED OR CHANGE OF OCCUPANCY PROVIDE NOTE ON THE
 PLAN THE PREVIOUS OCCUPANCY TYPE AND LOAD. PER FBC PL
 TABLE 403.1 AND FBC EX CH 7, 8, 9, 10
  
 9. THE WATER HEATER SHALL COMPLY WITH FBC ENERGY C404.2
 PLEASE PLACE NOTE ON THE PLAN.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  