2018-08-24 16:36:191ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18080413
 8/24/18
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M0.2 & M1.1: THE O/A CALCS AND PLAN SHOW TWO
 ROOMS THAT REQUIRE EXHAUST VENTILATION PER TABLE 403.3
 FBC M: THE ROOMS ARE THE LAB- 1.0 CFMS PER SF AND THE
 PHOTO- 1.0 CFMS PER SF. THE STORAGE ROOM MAY ALSO
 REQUIRE EXHAUST DEPENDING ON WHAT IS BEING STORED
 THERE. PLEASE PROVIDE A LIST OF ALL CHEMICALS OR
 MATERIALS TO BE STORED IN THE ROOM AND THEIR
 QUANTITIES- REFER TO SECTIONS 510.1- 510.10 FBC M.
  
 2) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 FAN COIL UNITS- SECTION C403.2.1 FBC-17 ENERGY
 CONSERVATION.
  
 3) SHEET M1.1 & M5.1: THERE IS A FIRE DAMPER
 INSTALLATION DETAIL ON THE PLAN. PLEASE INDICATE WHERE
 IT IS TO BE INSTALLED
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  