2018-08-23 16:02:12CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE FULL RISER DIAGRAM AND SHOW LOCATION ON SITE
 PLAN OF MAIN LOCATIONS. ALL MAINS SHOULD BE GROUPED.
 NEC 230.72; WPB FBC 107.2.1
 2. PROVIDE ACCURATE LOAD CALCULATION FOR EACH SERVICE
 MAIN PER ONE OF THE METHODS IN NEC 220. ESTIMATING THE
 LOAD BASED ON THE OCP SIZE IS NOT A PERMITTED METHOD,
 NOR IS A FUTURE DATA RECORDING. HOW IS IT POSSIBLE TO
 DESIGN THE SYSTEM WITHOUT KNOWING THE ACTUAL LOAD?
 PROVIDE COMPLIANCE. NEC 220
 3. PLAN STATES THAT THERE ARE 600 AMP FEEDERS TO
 WIREWAY, BUT THEN STATES TO UPGRADE TO COMPLY. THIS
 INDICATES THAT THE DESIGN PROFESSIONAL DOES NOT KNOW
 WHAT IS THERE. HOW IS IT POSSIBLE TO DESIGN WITHOUT
 KNOWING THE ACTUAL CAPACITY OF THE WIRING? PROVIDE
 CORRECTION. NEC 215.2, 215.5, 310.15; WPB FBC 107.2.1
 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10
 5. PROVIDE AIC RATING OF SERVICE DISCONNECTS AND
 PANELS. NEC 110.3, 110.9
 6. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF
 SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND
 AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24
 7. PROVIDE THE ESSENTIAL ELECTRICAL SYSTEMS REQUIRED
 FOR MEDICAL OFFICE. NEC 517.25, 517.45
 8. CONDUCTOR KEY NOTE 2 SHOWS AN EQUIPMENT GROUNDING
 CONDUCTOR (EGC). IF THIS IS A TAP FROM FPL FEED, AN EGC
 IS NOT PERMITTED. PROVIDE CORRECTION. NEC 250.6
 9. SOME RECEPTACLE OUTLETS ARE SHOWN WITHIN 6 FEET OF A
 SINK WITHOUT THE PROPER GFCI PROTECTION. PROVIDE
 CORRECTION. NEC 210.8
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  
 SINCERELY,
  
 JOHN PEARSON
 ELECTRICAL PLANS EXAMINER
 561-805-6746
 [email protected]
  