2018-08-23 16:02:12 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE FULL RISER DIAGRAM AND SHOW LOCATION ON SITE |
| PLAN OF MAIN LOCATIONS. ALL MAINS SHOULD BE GROUPED. |
| NEC 230.72; WPB FBC 107.2.1 |
| 2. PROVIDE ACCURATE LOAD CALCULATION FOR EACH SERVICE |
| MAIN PER ONE OF THE METHODS IN NEC 220. ESTIMATING THE |
| LOAD BASED ON THE OCP SIZE IS NOT A PERMITTED METHOD, |
| NOR IS A FUTURE DATA RECORDING. HOW IS IT POSSIBLE TO |
| DESIGN THE SYSTEM WITHOUT KNOWING THE ACTUAL LOAD? |
| PROVIDE COMPLIANCE. NEC 220 |
| 3. PLAN STATES THAT THERE ARE 600 AMP FEEDERS TO |
| WIREWAY, BUT THEN STATES TO UPGRADE TO COMPLY. THIS |
| INDICATES THAT THE DESIGN PROFESSIONAL DOES NOT KNOW |
| WHAT IS THERE. HOW IS IT POSSIBLE TO DESIGN WITHOUT |
| KNOWING THE ACTUAL CAPACITY OF THE WIRING? PROVIDE |
| CORRECTION. NEC 215.2, 215.5, 310.15; WPB FBC 107.2.1 |
| 4. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| NEC 110.9, 110.10 |
| 5. PROVIDE AIC RATING OF SERVICE DISCONNECTS AND |
| PANELS. NEC 110.3, 110.9 |
| 6. PROVIDE NOTES TO INDICATE THE REQUIRED MARKING OF |
| SERVICE EQUIPMENT FOR ARC FLASH HAZARD WARNING AND |
| AVAILABLE FAULT CURRENT PER CODE. NEC 110.16, 110.24 |
| 7. PROVIDE THE ESSENTIAL ELECTRICAL SYSTEMS REQUIRED |
| FOR MEDICAL OFFICE. NEC 517.25, 517.45 |
| 8. CONDUCTOR KEY NOTE 2 SHOWS AN EQUIPMENT GROUNDING |
| CONDUCTOR (EGC). IF THIS IS A TAP FROM FPL FEED, AN EGC |
| IS NOT PERMITTED. PROVIDE CORRECTION. NEC 250.6 |
| 9. SOME RECEPTACLE OUTLETS ARE SHOWN WITHIN 6 FEET OF A |
| SINK WITHOUT THE PROPER GFCI PROTECTION. PROVIDE |
| CORRECTION. NEC 210.8 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD |
| SHEETS?. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |