Date |
Text |
2018-08-14 14:44:48 | 08/14/2018 1ST PLUMBING/GAS REVIEW **DENIED** WITH |
| COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. PLEASE SIZE THE PIPE COMING OUT OF THE METER AND |
| PROVIDE TABLE. 2017 FBC FUEL GAS RES. SEC. G2413.4.1 |
| 2. THIS PLAN SHOWS A GAS GRILL. IS THE GAS GRILL PART |
| OF THE SYSTEM? SHOW THE TYPE OF PIPE MATERIAL BEING |
| INSTALLED FOR THE GRILL AND THE SIZE OF THE PIPE. WPB |
| AMENDMENTS TO FBC SEC.107.2.1 |
| 3. SUBMIT MANUFACTURES SPECIFICATIONS FOR THE GRILL AND |
| IF GRILL IS NOT BEING USED OR INSTALLED PLEASE REMOVE |
| FROM DRAWING LAYOUT. FGC SEC.305.1, FBC-RES. |
| SEC.G2408.1. |
| 4. SUBMIT MANUFACTURER?S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC.305.1 OR |
| 2017 FBC FUEL GAS RES. SEC. G2408.1. |
| 5. ON THE TWO COPIES OF A HOUSE PLAN SHOW THE LOCATION |
| OF THE TANKLESS WATER HEATER AND THE LOCATION AND |
| DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN RELATION |
| TO THE WATER HEATER. THE LOCATION OF THE WATER HEATER |
| SHALL COMPLY WITH THE MANUFACTURER'S INSTALLATION |
| INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND DRAWN. WPB |
| AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON |
| CONSTRUCTION DOCUMENTS. |
| 6. TOTAL JOB COST SEEMS LOW. THE VALUE MUST INCLUDE THE |
| COST OF ALL EQUIPMENT INCLUDING TANKLESS AND STOVE. |
| PROVIDE BONA FIDE SIGNED CONTRACT PER WPB AMENDMENTS TO |
| THE FBC 109.3 |
| 7. A SUB ELECTRICAL PERMIT MAY BE REQUIRED FOR SOURCE |
| OF IGNITION, WPB AMENDMENTS TO THE FBC SEC 105.1. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |