Plan Review Notes
Plan Review Notes For Permit 18080347
Permit Number 18080347
Review Stop G
Sequence Number 1
Notes
Date Text
2018-08-10 17:08:5108/10/2018 1ST PLUMBING/GAS REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE
 LENGTH OF ALL CUT SECTIONS OF PIPE OF EXISTING SYSTEM.
 THERE APPEARS TO BE A DIFFERENCE IN WHAT WAS SUBMITTED
 AND WHAT IS IN OUR RECORDS. I HAVE PUT TWO DIFFERENT
 PRIOR GAS DRAWINGS FOR REFREANCE ONLY, ONE SHOWS A POOL
 HEATER AT 400,000 BTU'S AND GAS GRILL 60,800 BTU'S IN
 2011 AND A SECOND ONE IN 2012 SHOWS AN OVEN AT 100,200
 BTU'S. WHAT YOU HAVE ON THE SUBMITTED ISOMETRIC DOES
 NOT MATCH, PLEASE REVIEW AND BRIEFLY THAT THE BTU LOAD
 OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL
 BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS
 PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST
 BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A
 GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF
 EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE
 PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE
 DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT
 OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF
 THE SECTION. 2017 FBC FUEL GAS RES SECS. G2413.4.1,
 G2413.4.2.
 2. PLEASE PUT THE ADDRESS AND CUSTOMER INFORMATION ON
 ISOMETRIC DRAWING, WPB AMENDMENTS TO THE FBC
 SEC.107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS.
 3. THE CODE ON THE ISOMETRIC REFERS TO 2014 AND WE ARE
 ON 2017, PLEASE UPDATE. WPB AMENDMENTS TO THE FBC SEC.
 107.2.1. INFORMATION ON CONSTRUCTION DOCUMENTS.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  