2018-08-08 17:59:15 | 08/08/2018 1ST GAS REVIEW **DENIED** WITH COMMENTS |
| |
| NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| |
| 1. SUBMIT A DETAIL SHOWING THE TYPE, LOCATION, SIZE, |
| TERMINATION POINT, HEIGHT ABOVE THE ROOF AND ANCHORING |
| DETAILS OF THE GAS VENT(S) PER 2017 FBC FUEL GAS SECS. |
| 502 THRU 505 OR 2017 FBC FUEL GAS RES. SECS. G2426 THRU |
| G2429.1 |
| 2. SUBMIT 2 COPIES OF MANUFACTURER?S SPECIFICATION |
| SHEETS/INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO |
| VERIFY COMPLIANCE WITH 2017 FBC FUEL GAS SEC.305.1 OR |
| 2017 FBC FUEL GAS RES. SEC. G2408.1. |
| 3. GAS APPLIANCES SHALL BE LISTED AND LABELED. THE |
| INSTALLATION MANUALS FOR ALL GAS APPLIANCES/EQUIPMENT |
| SHALL BE ONSITE AT THE TIME OF INSPECTION 2017 FBC FUEL |
| GAS SEC. 402.2 AND 301.3 OR 2017 FBC FUEL GAS RES. SEC. |
| G2413.2 AND G2404.3. |
| 4. THE GRILL IS LOCATED UNDER A ROOF; SUBMIT 2 COPIES |
| OF MANUFACTURES SPECIFICATIONS FOR THE GRILL IN WHICH |
| IT MAY REQUIRE A HOOD. FGC SEC.305.1, FBC-RES. |
| SEC.G2408.1. |
| 5. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| INSTALLATION. 2017 FBC FUEL GAS SEC.410.1 OR 2017 FBC |
| FUEL GAS RES. SEC. G2421.1. |
| 6. SUBMIT COMPLETE MANUFACTURER'S SPECIFICATIONS FOR |
| THE GAS DRYER. THE GAS DRYER SHALL BE LISTED AND |
| LABELED PER THE 2017 FBC FUEL GAS SEC.301.3 OR 2017 FBC |
| FUEL GAS RES. SEC. G2404.3. THE MANUFACTURER'S |
| SPECIFICATIONS SHALL NOTE THE CFM'S THAT ARE BEING |
| EXHAUSTED BY THE DRYER. |
| 7. PLEASE LABEL METER ON ISOMERIC WITH BIGGER FONTS, |
| WPB AMENDMENTS TO THE FBC SEC. 107.2.1.4 QUALITY OF |
| BUILDING PLANS. |
| |
| WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |