Plan Review Notes
Plan Review Notes For Permit 18080229
Permit Number 18080229
Review Stop G
Sequence Number 1
Notes
Date Text
2018-08-10 18:17:3508/10/2018 1ST PLUMBING/GAS REVIEW **DENIED** WITH
 COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. THE ISOMETRIC ON THE GENERATOR IS CALLING OUT A
 22KW/330 BTU AND YOUR APPLICATION IS FOR A 32KW, PLEASE
 CORRECT TO REFLECT CORRECT UNIT AS WELL AS ON THE
 MANUFACTURER'S SPECIFICATION SHEET. WPB AMENDMENTS TO
 THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
 2. PLEASE LABEL PLAN OF THE DISTANCE FOR GENERATOR,
 EXAMPLE; SHALL BE ONE FOOT SIX INCHES (1'-6") FROM THE
 HOUSE, FIVE (5'-0") FROM THE PROPERTY LINE, EXHAUST
 SHALL BE TEN (10'-0") FROM ANY OPENING UNLESS OTHERWISE
 STATED IN THE MANUFACTURES SPECIFICATION INSTRUCTIONS.
 WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON
 CONSTRUCTION DOCUMENTS
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  