Plan Review Notes For Permit 18080229 |
Permit Number |
18080229 |
|
Review Stop |
G |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-08-10 18:17:35 | 08/10/2018 1ST PLUMBING/GAS REVIEW **DENIED** WITH | | COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. THE ISOMETRIC ON THE GENERATOR IS CALLING OUT A | | 22KW/330 BTU AND YOUR APPLICATION IS FOR A 32KW, PLEASE | | CORRECT TO REFLECT CORRECT UNIT AS WELL AS ON THE | | MANUFACTURER'S SPECIFICATION SHEET. WPB AMENDMENTS TO | | THE FBC SEC.107.2.1 INFORMATION ON CONSTRUCTION | | DOCUMENTS. | | 2. PLEASE LABEL PLAN OF THE DISTANCE FOR GENERATOR, | | EXAMPLE; SHALL BE ONE FOOT SIX INCHES (1'-6") FROM THE | | HOUSE, FIVE (5'-0") FROM THE PROPERTY LINE, EXHAUST | | SHALL BE TEN (10'-0") FROM ANY OPENING UNLESS OTHERWISE | | STATED IN THE MANUFACTURES SPECIFICATION INSTRUCTIONS. | | WPB AMENDMENTS TO THE FBC SEC. 107.2.1. INFORMATION ON | | CONSTRUCTION DOCUMENTS | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS | | NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL | | REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE | | REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION | | PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO | | EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED | | COOPERATION. | | | | LUIS A. CRESPO | | PLUMBING INSPECTOR / | | PLUMBING PLAN REVIEW | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | [email protected] | | 561-805-6720 | | |
|