Plan Review Notes
Plan Review Notes For Permit 18080080
Permit Number 18080080
Review Stop E
Sequence Number 1
Notes
Date Text
2018-08-22 06:01:37ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ADDRESSING COMMENT OF "DEDICATED SIGN CIRCUIT AND
 TIME CLOCK BY OTHERS" WHO IS INSTALLING SIGN CIRCUIT?
 WHAT IS THE PERMIT #? WHERE IS THE PLAN WITH THE
 CONDUIT SIZE, WIRE SIZE, PANEL SCHEDULE ETC? NOT ENOUGH
 INFORMATION. FBC 107.2.1
  
 2. NO DISCONNECT WITHIN SIGHT OF SIGN TO DISCONNECT ALL
 UNGROUNDED CONDUCTORS FOR BRANCH CIRCUIT/FEEDER AT THE
 POINT WHICH IT ENTERS SIGN AS PER NEC 600.6A1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  