Plan Review Notes For Permit 18080079 |
Permit Number |
18080079 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-08-22 05:49:40 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. NO ELECTRICAL SUB-PERMIT APPLICATION FOR SIGN | | INCLUDED IN APPLICATION PACKET. PERMIT MUST BE PULLED | | BY AND EC OR ER REGISTERED TO PALM BEACH COUNTY. | | | | 2. HIGH VOLTAGE AND LOW VOLTAGE CANNOT BE TOGETHER IN | | J-BOX. 725.136B NEC | | | | 3. NO DISCONNECT WITHIN SIGHT OF SIGN TO DISCONNECT ALL | | UNGROUNDED CONDUCTORS OF BRANCH CIRCUIT/FEEDER BEFORE | | IT ENTERS SIGN AS PER 600.6A1 NEC | | | | | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | FRANK GIAQUINTO | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WPB | | [email protected] | | CELL: 561-657-1653 | | | | |
|