Plan Review Notes
Plan Review Notes For Permit 18080079
Permit Number 18080079
Review Stop E
Sequence Number 1
Notes
Date Text
2018-08-22 05:49:40ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. NO ELECTRICAL SUB-PERMIT APPLICATION FOR SIGN
 INCLUDED IN APPLICATION PACKET. PERMIT MUST BE PULLED
 BY AND EC OR ER REGISTERED TO PALM BEACH COUNTY.
  
 2. HIGH VOLTAGE AND LOW VOLTAGE CANNOT BE TOGETHER IN
 J-BOX. 725.136B NEC
  
 3. NO DISCONNECT WITHIN SIGHT OF SIGN TO DISCONNECT ALL
 UNGROUNDED CONDUCTORS OF BRANCH CIRCUIT/FEEDER BEFORE
 IT ENTERS SIGN AS PER 600.6A1 NEC
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved