2018-08-03 09:46:27RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS
 CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS.
  
 1- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR "ICE & WATER
 SHIELD" UNDERLAYMENT SPECIFIED ON THE "MEASUREMENTS"
 PAGE SUBMITTED TO VERIFY THAT UNDERLAYMENT IS DESIGNED
 FOR CONCRETE TILES WITH ADHESIVE INSTALLATIONS AS
 REQUIRED BY LIMITATION #5.4 OF ROOF TILE PRODUCT
 APPROVAL FL7473-R8 AND BY LIMITATION #5.5 OF ROOF TILE
 ADHESIVE PRODUCT APPROVAL FL6332-R8 SUBMITTED.
 FAC 61G20-3.001.
  
 2- CLEARLY MARK THE ADHESIVE PADDY SIZE ON TABLES 1 AND
 TABLE 2 OF ADHESIVE PRODUCT APPROVAL SUBMITTED AS
 REQUIRED BY CITY POLICY FOR ROOFING PERMITS TO VERIFY
 COMPLIANCE WITH PROPOSED INSTALLATION.
  