2018-09-18 07:59:171ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT. A-0.0.02 THE PLUMBING FIXTURE COUNT BREAKDOWN
 IS REFERENCING THE TENNIS CLUBHOUSE PLEASE CLARIFY. PER
 WPB AMEND TO FBC 107.2.1
  
 2. SHT. A-0.0.02 THE PLUMBING FIXTURE COUNT BREAKDOWN
 IS OVERLAPPING THE BUILDING HEIGHT DATA AND IS
 ILLEGIBLE PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 3. SHT. A -0.0.02 THE BUILDING OCCUPANCY IS MISSING THE
 NUMBER OF PEOPLE PLEASE CLARIFY. PER WPB AMEND TO FBC
 107.2.1
  
 4. SHT. A-4.1.02 DETAILS # 2,3,10 KEY # 1,2 HAVE
 PRINTING OVER THE TOP OF THEM RENDERING THEM ILLEGIBLE
 PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 5. SHT. A-7.0.01 THE TEXT, LABELS AND DIMENSIONS ARE TO
 LIGHT READ PLEASE DARKEN . PER WPB AMEND TO FBC 107.2.1
  
 6. SHT. P-3.0.00 + P-1.4.01 THE MOP SINK IS NOT VENTED
 SHALL COMPLY WITH FBC PL 901.2.1
  
 7. SHT. P-4.0.00 DETAIL #4 SHOWS A HUB DRAIN IT IS NOT
 SHOWN ON THE FLOOR PLAN OR ISOMETRIC PLEASE CLARIFY.
 PER WPB AMEND TO FBC 107.2.1
  
 8. SHT. P-4.0.00 DETAIL #6 SHOWS SHOCK ARRESTORS PLEASE
 SHOW LOCATION ON WATER ISOMETRIC. PER WPB AMEND TO FBC
 107.2.1
  
 9. SHT. P-4.0.00 DETAIL #4 SHOW SIZE OF EXPANSION TANK.
 PER WPB AMEND TO FBC 107.2.1
  
 10. PROVIDE A PLUMBING FIXTURE BREAK DOWN TO SHOW WHY
 THE MENS FIXTURE COUNT IS HIGHER THAN THE WOMENS SHALL
 COMPLY WITH FBC PL TABLE 403.1 AND SEC 403.1.1
  
 11. PROVIDE A SITE PLAN SHOWING THE WATER METER AND
 BACK FLOW. PER WPB AMEND TO FBC 107.2.1
  
 12. PLEASE PROVIDE APPROVAL FOR THE RELOCATED FUEL TANK
 FROM PALM BEACH COUNTY DEPARTMENT OF ENVIRONMENTAL
 RESOURCES.
  
 13. PROVIDE DOCUMENTATION DECLARING THE CALCIFICATION
 OF THE LIQUID FUELS AND CHEMICALS. PER WPB AMEND TO FBC
 107.2.1. EDITIONAL INFORMATION NEEDED
  
 14. PROVIDE MSDS SHEETS FOR THE FERTILIZERS, CHEMICALS
 AND FUELS BEING USED ON THIS PROPERTY. PER WPB AMEND TO
 FBC 107.2.1
  
 15. PLEASE PROVIDE THE AMOUNTS, HOW THERE BEING STORED
 AND EXACT LOCATION OF ALL FERTILIZERS, CHEMICALS AND
 FUELS BEING USED ON THIS PROPERTY. PER WPB AMEND TO FBC
 107.2.1
  
 16. SHOW COMPLIANCE ON THE PLAN WITH NFPA 30 AND 101
  
 17. PROVIDE PLUMBING PLAN AND ISOMETRIC FOR ALL PIPING
 IN THE COVERED EQUIPMENT AREA AND FUEL STORAGE ALSO THE
 FERTILIZER STORAGE BUILDING. PER WPB AMEND TO FBC
 107.2.1
  
 18. PROVIDE MANUFACTURE SPECIFICATIONS FOR ALL
 EQUIPMENT. PER WPB AMEND TO FBC 107.2.1
  
 19. A SAND OIL SEPARATOR IS REQUIRED FOR DRAINS FROM
 COVERED EQUIPMENT BUILDING. FBC PL 1003.4
  
 20. SHT A-1.4.03 SHOWS COMPRESSED AIR PLEASE PROVIDE A
 FLOOR PLAN AND RISER DIAGRAM SHOW PIPING TYPE AND SIZE.
 PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711