2018-09-18 07:59:17 | 1ST REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. SHT. A-0.0.02 THE PLUMBING FIXTURE COUNT BREAKDOWN |
| IS REFERENCING THE TENNIS CLUBHOUSE PLEASE CLARIFY. PER |
| WPB AMEND TO FBC 107.2.1 |
| |
| 2. SHT. A-0.0.02 THE PLUMBING FIXTURE COUNT BREAKDOWN |
| IS OVERLAPPING THE BUILDING HEIGHT DATA AND IS |
| ILLEGIBLE PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 3. SHT. A -0.0.02 THE BUILDING OCCUPANCY IS MISSING THE |
| NUMBER OF PEOPLE PLEASE CLARIFY. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| 4. SHT. A-4.1.02 DETAILS # 2,3,10 KEY # 1,2 HAVE |
| PRINTING OVER THE TOP OF THEM RENDERING THEM ILLEGIBLE |
| PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| |
| 5. SHT. A-7.0.01 THE TEXT, LABELS AND DIMENSIONS ARE TO |
| LIGHT READ PLEASE DARKEN . PER WPB AMEND TO FBC 107.2.1 |
| |
| 6. SHT. P-3.0.00 + P-1.4.01 THE MOP SINK IS NOT VENTED |
| SHALL COMPLY WITH FBC PL 901.2.1 |
| |
| 7. SHT. P-4.0.00 DETAIL #4 SHOWS A HUB DRAIN IT IS NOT |
| SHOWN ON THE FLOOR PLAN OR ISOMETRIC PLEASE CLARIFY. |
| PER WPB AMEND TO FBC 107.2.1 |
| |
| 8. SHT. P-4.0.00 DETAIL #6 SHOWS SHOCK ARRESTORS PLEASE |
| SHOW LOCATION ON WATER ISOMETRIC. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| 9. SHT. P-4.0.00 DETAIL #4 SHOW SIZE OF EXPANSION TANK. |
| PER WPB AMEND TO FBC 107.2.1 |
| |
| 10. PROVIDE A PLUMBING FIXTURE BREAK DOWN TO SHOW WHY |
| THE MENS FIXTURE COUNT IS HIGHER THAN THE WOMENS SHALL |
| COMPLY WITH FBC PL TABLE 403.1 AND SEC 403.1.1 |
| |
| 11. PROVIDE A SITE PLAN SHOWING THE WATER METER AND |
| BACK FLOW. PER WPB AMEND TO FBC 107.2.1 |
| |
| 12. PLEASE PROVIDE APPROVAL FOR THE RELOCATED FUEL TANK |
| FROM PALM BEACH COUNTY DEPARTMENT OF ENVIRONMENTAL |
| RESOURCES. |
| |
| 13. PROVIDE DOCUMENTATION DECLARING THE CALCIFICATION |
| OF THE LIQUID FUELS AND CHEMICALS. PER WPB AMEND TO FBC |
| 107.2.1. EDITIONAL INFORMATION NEEDED |
| |
| 14. PROVIDE MSDS SHEETS FOR THE FERTILIZERS, CHEMICALS |
| AND FUELS BEING USED ON THIS PROPERTY. PER WPB AMEND TO |
| FBC 107.2.1 |
| |
| 15. PLEASE PROVIDE THE AMOUNTS, HOW THERE BEING STORED |
| AND EXACT LOCATION OF ALL FERTILIZERS, CHEMICALS AND |
| FUELS BEING USED ON THIS PROPERTY. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| 16. SHOW COMPLIANCE ON THE PLAN WITH NFPA 30 AND 101 |
| |
| 17. PROVIDE PLUMBING PLAN AND ISOMETRIC FOR ALL PIPING |
| IN THE COVERED EQUIPMENT AREA AND FUEL STORAGE ALSO THE |
| FERTILIZER STORAGE BUILDING. PER WPB AMEND TO FBC |
| 107.2.1 |
| |
| 18. PROVIDE MANUFACTURE SPECIFICATIONS FOR ALL |
| EQUIPMENT. PER WPB AMEND TO FBC 107.2.1 |
| |
| 19. A SAND OIL SEPARATOR IS REQUIRED FOR DRAINS FROM |
| COVERED EQUIPMENT BUILDING. FBC PL 1003.4 |
| |
| 20. SHT A-1.4.03 SHOWS COMPRESSED AIR PLEASE PROVIDE A |
| FLOOR PLAN AND RISER DIAGRAM SHOW PIPING TYPE AND SIZE. |
| PER WPB AMEND TO FBC 107.2.1 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |