2018-08-08 12:41:24 | PERMIT # 18080066 |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| 1) UPDATE THE CODE LIST TO REFERENCE THE 6TH EDITION OF |
| THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| 2015 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| AMENDMENTS. |
| |
| 2) PROVIDE PERMANENT WEATHERPROOF DIAMOND PLACARDS PER |
| NFPA 704 INDICATING THE HEALTH, FLAMMABILITY AND |
| REACTIVITY RATING OF THE HAZARDOUS MATERIALS. PLACARDS |
| SHALL BE LOCATED ON |
| (1) STATIONARY ABOVEGROUND TANKS |
| (2) STATIONARY ABOVEGROUND CONTAINERS |
| (3) AT ENTRANCES TO LOCATIONS WHERE HAZARDOUS MATERIALS |
| ARE STORED, DISPENSED, USED, OR HANDLED IN QUANTITIES |
| REQUIRING A PERMIT |
| (4) AT OTHER ENTRANCES AND LOCATIONS DESIGNATED BY THE |
| FIRE DEPARTMENT |
| |
| 3) PROVIDE THE CLASSIFICATION OF HAZARD OCCUPANCY FOR |
| EACH ROOM OR AREA, AS DEFINED UNDER THE FLORIDA FIRE |
| PREVENTION CODE (FFPC). |
| |
| 4) PLEASE PROVIDE A DETAILED NARRATIVE REGARDING THE |
| TYPE OF WORK AND STORAGE THAT WILL BE CONDUCTED WITHIN |
| THE MAINTENANCE BUILDING. FOR EXAMPLE, WILL THERE BE |
| FUEL STORAGE, VEHICLE REPAIR AND MAINTENANCE, EQUIPMENT |
| REPAIR AND MAINTENANCE. ETC. |
| |
| 5) STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS |
| CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO |
| THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF |
| DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA |
| ADMINISTRATIVE CODE 69A-60.0081. |
| |
| 6) PLEASE PROVIDE AN INVENTORY DETAIL OF THE ITEMS TO |
| BE STORED IN THE CHEMICAL AND FERTILIZER STORAGE AREAS. |
| THIS SHOULD INCLUDE, BUT IS NOT LIMITED TO, |
| MANUFACTURER SPEC SHEETS, QUANTITIES, STORAGE METHOD |
| (RACKS, CONTAINERS, ETC.), CONTAINMENT METHOD, HAZARD |
| OF CONTENTS (NFPA 101: 6.2)....ETC. |
| |
| 7) SHEET A1.0.01: A FIRE RATED SEPARATION MAY BE |
| REQUIRED BETWEEN THE CHEMICAL STORAGE AND FERTILIZER |
| STORAGE ROOMS. THIS WILL BE DETERMINED ONCE THE HAZARD |
| OF CONTENTS IS PROVIDED. |
| |
| 8) PROVIDE A LIFE SAFETY PLAN SHOWING ALL OCCUPANCY |
| TYPES, OCCUPANT LOADS, FIRE RATED WALLS, EXIT SIGNS, |
| EMERGENCY LIGHTING, TRAVEL DISTANCES, COMMON PATH OF |
| TRAVEL ETC. |
| |
| A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED |
| AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON |
| THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED DURING PLAN RESUBMISSION. |
| |
| |