2018-09-20 08:08:47 | ****CORRECTIONS**** |
| W.P.B. PERMIT: 18080066 |
| REVIEWED: SEPTEMBER 19, 2018 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER I |
| [email protected] |
| 561-805-6718 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC ENERGY = FBC ENERGY CONSERVATION |
| |
| 1.[FBC AMENDED 105]SEPARATE PERMIT WILL BE REQUIRED FOR |
| EACH STRUCTURE. THIS REVIEW WILL BE A GENERAL REVIEW OF |
| ALL THREE BUILDINGS, BUT THE STORAGE BUILDING AND THE |
| FUEL CANOPY WILL NEED A STAND ALONE PERMITS. |
| ALSO, SEPARATE PERMITS REQUIRED FOR FENCING, TRASH |
| ENCLOSURE AND PERMIT THROUGH ENGINEERING FOR DRIVEWAY |
| ACCESS (CIVIL). |
| |
| 2.[FBC 107.3.5.1.1]PROVIDE SITE DRAINAGE PLAN. THIS CAN |
| BE FROM CIVIL PLANS (ONLY INCLUDE CIVIL PLANS RELEVANT |
| TO THIS SITE). |
| |
| 3.[FBC 107.3.5.3]PROVIDE SEDIMENT CONTROL PLAN TO KEEP |
| CONSTRUCTION DEBRIS FROM ENTERING ADJACENT PROPERTIES |
| AND STORM DRAINS DURING CONSTRUCTION. YOU CAN FIND |
| ENGINEERING STANDARD DETAILS FROM WPB WEBSITE-POLLUTION |
| CONTROL |
| HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS |
| /FORMS,-PERMITS-APPLICATIONS |
| |
| 4.[FL. STATUTE 472]SURVEY TO BE SIGNED AND SEALED BY |
| THE SURVEYOR OF RECORD. PROVIDE COPY OF SURVEY PRODUCED |
| BY THE SURVEYOR OF RECORD. |
| |
| 5.[FBC 107.2.5]PROVIDE A LIFE SAFETY SHEET WITH |
| BREAKDOWN FOR BOTH OCCUPANCIES IN THE MAINTENANCE BLDG. |
| |
| 6.[FBC 107.2.5]ADD NEW LIFE SAFETY SHEET AND SHEET |
| S3.01 TO INDEX. THIS SHEET WILL RECEIVE DIGITAL STAMP |
| FOR BUILDING REVIEW AND I WOULD LIKE ALL SHEETS |
| PROVIDED TO BE LISTED ON THAT PAGE. |
| |
| 7.[FBC ENERGY C401.2]APPLICATION. |
| COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE |
| FOLLOWING: |
| 1.THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, EXCLUDING |
| SECTION 9.4.1.1(G) OF THE STANDARD. |
| 2.THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN |
| ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH |
| SECTION C406 AND TENANT SPACES SHALL COMPLY WITH |
| SECTION C406.1.1. |
| 3.THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404, |
| C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING |
| ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT |
| OF THE STANDARD REFERENCE DESIGN BUILDING. |
| |
| 8.[FBC 107.2.5]SHEET A-0.0.02 SHOULD INCLUDE OCCUPANCY |
| DATA FOR ADMINISTRATION AREA. |
| |
| 9.[FBC 311.2]THE MAINTENANCE PORTION SHOULD BE |
| RE-CLASSIFIED AS S-1 BECAUSE IT FALLS UNDER REPAIR |
| GARAGE AND IS NOT JUST STORAGE MATERIALS THAT FALL |
| UNDER S-2. |
| |
| 10.[FBC [F]406.8.6]PLEASE ADJUST ALL PLANS TO |
| INCORPORATE THE OCCUPANCY INCLUDING THE ADDITION OF |
| FIRE SPRINKLERS IN THE S-2 OCCUPANCY AND SEPERATION OF |
| OCCUPANCIES AS REQUIRED IN SECTION 602 CONSTRUCTION |
| CLASSIFICATION. |
| |
| 11.[FBC ACCESSIBILITY 804.3.2]HEIGHT. THE KITCHEN WORK |
| SURFACE SHALL BE 34 INCHES (865 MM) MAXIMUM ABOVE THE |
| FINISH FLOOR OR GROUND. |
| PROVIDE DETAILS OF BREAK AREA CABINETRY. |
| |
| 12.[FBC 1609.6.4.4.1]COMPONENTS AND CLADDING. |
| SHEET S-5.00 UPDATE CODE REFERENCES TO FBC 2017 6TH |
| EDITION. |
| PROVIDE +/- PRESSURES FOR EACH OPENING. |
| |
| 13.SHEET A-3.2.01 CALLS OUT 5/8 PLYWOOD, BUT |
| STRUCTURALS ARE CALLING 3/4. PLEASE CO-ORDINATE THE |
| PLYWOOD SIZE. |
| |
| NOTE: FULL REVIEW CANNOT BE COMPLETED AT THIS TIME. |
| UPON RE-SUBMITTAL A FULL REVIEW WILL BE DONE UNDER THE |
| ESTABLISHED OCCUPANCY CLASSIFICATION. |
| |
| |
| PRODUCT APPROVALS (APPLIES TO ALL STRUCTURES): |
| |
| 14.[FBC AMENDED 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR |
| WINDOWS, DOORS, AND ROLL-UP DOORS, OR INDICATE THAT YOU |
| WOULD LIKE THEM DEFFERED. |
| |
| 15.[FBC AMENDED 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR |
| ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM DEFFERED. |
| |
| 16. DELETED |
| |
| |
| FERTILIZER STORAGE SPECIFIC COMMENTS: |
| |
| 17.[FBC SECTION 307]S-2 STORAGE MAY NOT BE APPROPRIATE |
| FOR THE STORAGE NEEDS OF THE STRUCTURE. PLEASE REVIEW |
| SECTION 307 AND DETERMINE WHAT OCCUPANCY CLASSIFICATION |
| IS APPROPRIATE. |
| IF GROUP H CLASSIFICATION IS ESTABLISHED, USE SECTION |
| 415 FOR SPECIAL REQUIREMENTS BASED ON H CLASSIFICATION. |
| |
| 18.[FBC 1507.4.2]DECK SLOPE. THE MINIMUM SLOPE FOR |
| LAPPED, NONSOLDERED SEAM METAL ROOF PANELS WITHOUT |
| APPLIED LAP SEALANT SHALL BE THREE UNITS VERTICAL IN 12 |
| UNITS HORIZONTAL (25-PERCENT SLOPE). |
| ADD NOTE THAT METAL PANELS WILL HAVE APPLIED LAP |
| SEALANT. |
| |
| NOTE: FULL REVIEW CANNOT BE COMPLETED AT THIS TIME. |
| UPON RE-SUBMITTAL A FULL REVIEW WILL BE DONE UNDER THE |
| ESTABLISHED OCCUPANCY CLASSIFICATION. |
| |
| |
| FUEL CANOPY SPECIFIC COMMENTS: |
| |
| 19.[FBC SECTION 302]PROVIDE AN OCCUPANCY CLASSIFICATION |
| FOR THIS STRUCTURE. |
| |
| 20.[FBC 1507.4.2]DECK SLOPE. THE MINIMUM SLOPE FOR |
| LAPPED, NONSOLDERED SEAM METAL ROOF PANELS WITHOUT |
| APPLIED LAP SEALANT SHALL BE THREE UNITS VERTICAL IN 12 |
| UNITS HORIZONTAL (25-PERCENT SLOPE). |
| ADD NOTE THAT METAL PANELS WILL HAVE APPLIED LAP |
| SEALANT. |
| |
| NOTE: FULL REVIEW CANNOT BE COMPLETED AT THIS TIME. |
| UPON RE-SUBMITTAL A FULL REVIEW WILL BE DONE UNDER THE |
| ESTABLISHED OCCUPANCY CLASSIFICATION. |
| |
| |
| DUMPSTER ENCLOSURE AND SOIL BINS SPECIFIC COMMENTS: |
| |
| 21. PROVIDE DETAILS FOR THESE STRUCTURES. SINCE DUMSTER |
| ENCLOSURE IS SEPARATE PERMIT INCLUDE THE SOIL BINS WITH |
| IT SINCE THEY ARE CONNECTED. |
| |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |