Plan Review Notes
Plan Review Notes For Permit 18080066
Permit Number 18080066
Review Stop B
Sequence Number 1
Notes
Date Text
2018-09-20 08:08:47****CORRECTIONS****
 W.P.B. PERMIT: 18080066
 REVIEWED: SEPTEMBER 19, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
  
 1.[FBC AMENDED 105]SEPARATE PERMIT WILL BE REQUIRED FOR
 EACH STRUCTURE. THIS REVIEW WILL BE A GENERAL REVIEW OF
 ALL THREE BUILDINGS, BUT THE STORAGE BUILDING AND THE
 FUEL CANOPY WILL NEED A STAND ALONE PERMITS.
 ALSO, SEPARATE PERMITS REQUIRED FOR FENCING, TRASH
 ENCLOSURE AND PERMIT THROUGH ENGINEERING FOR DRIVEWAY
 ACCESS (CIVIL).
  
 2.[FBC 107.3.5.1.1]PROVIDE SITE DRAINAGE PLAN. THIS CAN
 BE FROM CIVIL PLANS (ONLY INCLUDE CIVIL PLANS RELEVANT
 TO THIS SITE).
  
 3.[FBC 107.3.5.3]PROVIDE SEDIMENT CONTROL PLAN TO KEEP
 CONSTRUCTION DEBRIS FROM ENTERING ADJACENT PROPERTIES
 AND STORM DRAINS DURING CONSTRUCTION. YOU CAN FIND
 ENGINEERING STANDARD DETAILS FROM WPB WEBSITE-POLLUTION
 CONTROL
 HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-WORKS
 /FORMS,-PERMITS-APPLICATIONS
  
 4.[FL. STATUTE 472]SURVEY TO BE SIGNED AND SEALED BY
 THE SURVEYOR OF RECORD. PROVIDE COPY OF SURVEY PRODUCED
 BY THE SURVEYOR OF RECORD.
  
 5.[FBC 107.2.5]PROVIDE A LIFE SAFETY SHEET WITH
 BREAKDOWN FOR BOTH OCCUPANCIES IN THE MAINTENANCE BLDG.
  
 6.[FBC 107.2.5]ADD NEW LIFE SAFETY SHEET AND SHEET
 S3.01 TO INDEX. THIS SHEET WILL RECEIVE DIGITAL STAMP
 FOR BUILDING REVIEW AND I WOULD LIKE ALL SHEETS
 PROVIDED TO BE LISTED ON THAT PAGE.
  
 7.[FBC ENERGY C401.2]APPLICATION.
 COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE
 FOLLOWING:
 1.THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, EXCLUDING
 SECTION 9.4.1.1(G) OF THE STANDARD.
 2.THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN
 ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH
 SECTION C406 AND TENANT SPACES SHALL COMPLY WITH
 SECTION C406.1.1.
 3.THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404,
 C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING
 ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT
 OF THE STANDARD REFERENCE DESIGN BUILDING.
  
 8.[FBC 107.2.5]SHEET A-0.0.02 SHOULD INCLUDE OCCUPANCY
 DATA FOR ADMINISTRATION AREA.
  
 9.[FBC 311.2]THE MAINTENANCE PORTION SHOULD BE
 RE-CLASSIFIED AS S-1 BECAUSE IT FALLS UNDER REPAIR
 GARAGE AND IS NOT JUST STORAGE MATERIALS THAT FALL
 UNDER S-2.
  
 10.[FBC [F]406.8.6]PLEASE ADJUST ALL PLANS TO
 INCORPORATE THE OCCUPANCY INCLUDING THE ADDITION OF
 FIRE SPRINKLERS IN THE S-2 OCCUPANCY AND SEPERATION OF
 OCCUPANCIES AS REQUIRED IN SECTION 602 CONSTRUCTION
 CLASSIFICATION.
  
 11.[FBC ACCESSIBILITY 804.3.2]HEIGHT. THE KITCHEN WORK
 SURFACE SHALL BE 34 INCHES (865 MM) MAXIMUM ABOVE THE
 FINISH FLOOR OR GROUND.
 PROVIDE DETAILS OF BREAK AREA CABINETRY.
  
 12.[FBC 1609.6.4.4.1]COMPONENTS AND CLADDING.
 SHEET S-5.00 UPDATE CODE REFERENCES TO FBC 2017 6TH
 EDITION.
 PROVIDE +/- PRESSURES FOR EACH OPENING.
  
 13.SHEET A-3.2.01 CALLS OUT 5/8 PLYWOOD, BUT
 STRUCTURALS ARE CALLING 3/4. PLEASE CO-ORDINATE THE
 PLYWOOD SIZE.
  
 NOTE: FULL REVIEW CANNOT BE COMPLETED AT THIS TIME.
 UPON RE-SUBMITTAL A FULL REVIEW WILL BE DONE UNDER THE
 ESTABLISHED OCCUPANCY CLASSIFICATION.
  
  
 PRODUCT APPROVALS (APPLIES TO ALL STRUCTURES):
  
 14.[FBC AMENDED 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR
 WINDOWS, DOORS, AND ROLL-UP DOORS, OR INDICATE THAT YOU
 WOULD LIKE THEM DEFFERED.
  
 15.[FBC AMENDED 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR
 ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM DEFFERED.
  
 16. DELETED
  
  
 FERTILIZER STORAGE SPECIFIC COMMENTS:
  
 17.[FBC SECTION 307]S-2 STORAGE MAY NOT BE APPROPRIATE
 FOR THE STORAGE NEEDS OF THE STRUCTURE. PLEASE REVIEW
 SECTION 307 AND DETERMINE WHAT OCCUPANCY CLASSIFICATION
 IS APPROPRIATE.
 IF GROUP H CLASSIFICATION IS ESTABLISHED, USE SECTION
 415 FOR SPECIAL REQUIREMENTS BASED ON H CLASSIFICATION.
  
 18.[FBC 1507.4.2]DECK SLOPE. THE MINIMUM SLOPE FOR
 LAPPED, NONSOLDERED SEAM METAL ROOF PANELS WITHOUT
 APPLIED LAP SEALANT SHALL BE THREE UNITS VERTICAL IN 12
 UNITS HORIZONTAL (25-PERCENT SLOPE).
 ADD NOTE THAT METAL PANELS WILL HAVE APPLIED LAP
 SEALANT.
  
 NOTE: FULL REVIEW CANNOT BE COMPLETED AT THIS TIME.
 UPON RE-SUBMITTAL A FULL REVIEW WILL BE DONE UNDER THE
 ESTABLISHED OCCUPANCY CLASSIFICATION.
  
  
 FUEL CANOPY SPECIFIC COMMENTS:
  
 19.[FBC SECTION 302]PROVIDE AN OCCUPANCY CLASSIFICATION
 FOR THIS STRUCTURE.
  
 20.[FBC 1507.4.2]DECK SLOPE. THE MINIMUM SLOPE FOR
 LAPPED, NONSOLDERED SEAM METAL ROOF PANELS WITHOUT
 APPLIED LAP SEALANT SHALL BE THREE UNITS VERTICAL IN 12
 UNITS HORIZONTAL (25-PERCENT SLOPE).
 ADD NOTE THAT METAL PANELS WILL HAVE APPLIED LAP
 SEALANT.
  
 NOTE: FULL REVIEW CANNOT BE COMPLETED AT THIS TIME.
 UPON RE-SUBMITTAL A FULL REVIEW WILL BE DONE UNDER THE
 ESTABLISHED OCCUPANCY CLASSIFICATION.
  
  
 DUMPSTER ENCLOSURE AND SOIL BINS SPECIFIC COMMENTS:
  
 21. PROVIDE DETAILS FOR THESE STRUCTURES. SINCE DUMSTER
 ENCLOSURE IS SEPARATE PERMIT INCLUDE THE SOIL BINS WITH
 IT SINCE THEY ARE CONNECTED.
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  