Date Text
2018-08-31 11:58:01****PROVISOS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 A. SHEETS GG102 AND GA102 WHICH WERE REVIEWED BY EMAIL
 ARE TO BE SUBMITTED AS A REVISION WITHIN 3 BUSINESS
 DAYS AFTER PERMIT ISSUANCE (BY 9/6/18).
  
 B. THE PRIVATE PROVIDER'S STAMP IS MISSING FROM MANY
 PAGES AND THE VERSION CALLED OUT ON THE PLAN COMPLIANCE
 AFFIDAVIT IS NOT CONSISTENT WITH THE VERSION REVIEWED.
 SUBMIT ONE SET STAMPED BY THE PRIVATE PROVIDER WITH AN
 UPDATED PLAN REVIEW COMPLIANCE AFFIDAVIT. IT IS
 RECOMMENDED THAT YOU HAVE THEM STAMP A COPY OF THE
 ISSUED PERMIT SET.
  
 C. THIS PERMIT IS ISSUED AT APPLICANT'S RISK PER FBC
 105.13:
  
 PHASED PERMIT APPROVAL. AFTER SUBMITTAL OF THE
 APPROPRIATE CONSTRUCTION DOCUMENTS, THE BUILDING
 OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR THE
 CONSTRUCT ION OF FOUNDATIONS OR ANY OTHER PART OF A
 BUILDING OR STRUCTURE BEFORE THE CONSTRUCTION DOCUMENTS
 FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN
 SUBMITTED. THE HOLDER OF SUCH PERMIT FOR THE FOUNDATION
 OR OTHER PARTS OF A BUILDING OR STRUCTURE SHALL PROCEED
 AT THE HOLDER'S OWN RISK WITH THE BUILDING OPERATION
 AND WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED. CORRECTIONS MAY BE REQUIRED
 TO MEET THE REQUIREMENTS OF THE TECHNICAL CODES. THIS
 PROVISION IS ONLY FOR THE FLORIDA BUILDING CODE. ALL
 OTHER AGENCY APPROVALS NECESSARY FOR CONSTRUCTION MUST
 BE SECURED PRIOR TO THIS PROVISION BEING APPLIED.
  
 D. ADVISORY FOR BUILDING PERMIT:
 SHORING/RESHORE ENGINEERING IS TO BE SUBMITTED,
 REVIEWED AND ISSUED PRIOR TO INSTALLATION.
 FAILURE TO DO SO ***WILL*** RESULT IN A STOP WORK ORDER
 IF CONTRACTOR PROCEEDS WITHOUT SUBMITTAL OF
 SHORING/RESHORE ENGINEERING (#7, PAGE 4,
 THRESHOLD/SPECIAL INSPECTOR OBLIGATIONS IN THE
 AGREEMENT SIGNED BY ALL PARTIES).
  
 E. ADVISORY FOR BUILDING PERMIT:
 AN ENGINEERED CONSTRUCTION GUARD RAIL DETAIL IS
 REQUIRED PRIOR TO INSTALLATION. THIS IS TO BE SUBMITTED
 WITH THE SHORING/RESHORE ENGINEERING, BUT SUBJECT TO
 FIELD INSPECTOR'S DISCRETION CAN BE PROVIDED IN THE
 FIELD.
  
  
  