Plan Review Notes For Permit 18071472 |
Permit Number |
18071472 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-08-14 10:02:29 | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 | | 6TH ED, CHAPTER 1. | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | | | 1. PROVIDE RISER DIAGRAM, SHOWING ALL DETAILS OF | | SERVICE EQUIPMENT, UNDERGROUND OR OVERHEAD SERVICE, | | WIRE AND BREAKER SIZES FOR SERVICE AND FEED TO ANY | | SUB-PANEL(S). SHOW GEC SIZE AND SYSTEM, SHOW | | INTERSYSTEM BONDING TERMINATION POINT. NEC 215.5, 230, | | 250.50, 250.94, 408.30 | | 2. PROVIDE LOAD CALCULATION FOR SERVICE TO CONFIRM | | CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY | | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED | | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD | | SHEETS?. | | | | SINCERELY, | | | | JOHN PEARSON | | ELECTRICAL PLANS EXAMINER | | 561-805-6746 | | [email protected] | | |
|