Plan Review Notes For Permit 18071468 |
Permit Number |
18071468 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-08-08 14:53:42 | 1) SUBMIT MANUFACTURER'S SPECIFICATIONS & INSTALLATION | | MANUAL FOR THE BATHTUB.THE BATHTUB SHALL COMPLY WITH | | THE STANDARDS LISTED IN 2017 FBC-RESIDENTIAL TABLE | | P2701.1. | | 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE BATHTUB | | VALVE. HOT WATER SSUPPLIED TO BATHTUBS SHALL BE LIMITED | | TO 120 DEGREES FAHRENHEIT AND SHALL COMPLY WITH THE | | REQUIREMENTS OF 2017 FBC-RESIDENTIAL SEC.P2713.3. | | 3) THE SUBMITTED PLUMBING RISER SHOWS A FLAT, DRY VENT | | FOR THE TUB WHICH IS NOT PERMITTED PER THE 2017 FBC- | | RES. SEC. P3104.3. | | 4) THE SUBMITTED FLOOR PLAN SHOWS THE TUB BEING | | INSTALLED IN A DRESSING ROOM. THIS WOULD NOW BE | | CONSIDERED A BATHROOM AND COMPLY WITH 2017 FBC-RES.SEC. | | R303.3 FOR REQUIRED AGGREGATE GLAZING AND VENTILATION | | REQUIREMENTS. REFER TO THE EXCEPTION FOR ALTERNATE | | COMPLIANCE. | | 5) INDICATE ON THE PLAN IF ANY OTHER WORK WILL BE | | ASSOCIATED WITH THIS INSTALLATION ( BUILDING, | | ELECTRICAL, ETC.) AND IF SO SUBMIT A COMPLETE SET OF | | PLANS THAT REFLECT THE ENTIRE SCOPE OF WORK TO BE DONE. | | WPB AMEND. TO FBC SEC. 107.2.1. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|