Plan Review Notes For Permit 18071458 |
Permit Number |
18071458 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-08-13 11:08:49 | ****CORRECTIONS**** | | W.P.B. PERMIT: 18071458 | | REVIEWED: AUGUST 13, 2018 | | | | DYLAN BATTLES | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC EB = FBC EXISTING BUILDING | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | SHEET A-2 IN DESIGN PARAMETERS, THE CODE FOR THIS | | PROJECT SHOULD BE FBC 2017 6TH EDITION. | | | | SHEET A-2 REFERS TO (SEE ENERGY CALCS). ARE THESE TO BE | | PROVIDED, OR IS THE REPAIR WORK FOLLOWING PRESCRIPTIVE | | METHOD? | | | | PLEASE PROVIDE MORE DETAIL OF THE REPAIR WORK TO BE | | DONE. THE PLANS DON?T SHOW ENOUGH ABOUT REPAIRS TO BE | | COMPLETED TO MATCH THE $60,000.00 VALUE OF PROJECT. DID | | THE FIRE BURN THROUGH THE ROOF? | | | | NOTE: | | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW | | EACH COMMENT IS BEING ADDRESSED. | | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW | | OF MATERIALS REQUESTED. | | |
|