Plan Review Notes For Permit 18071389 |
Permit Number |
18071389 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-08-02 15:04:22 | PLAN DENIED | | 1) REFER TO SECTION 107.2.1 INFORMATION ON CONSTRUCTION | | DOCUMENTS. | | ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DETA SHALL | | BEAR THE NAME AND SIGNATURE OF THE PERSON RESPONSIBLE | | FOR THE DESIGN. | | 2014 FBC. | | 2) REFER TO SECTION 107.3.5.1.4 MECHANICAL. # 3 PROVIDE | | EQUIPMENT SCHEDULE | | ON THE PLAN. 2017 FBC | | 3) CLARIFY ON THE PLAN IF THE RETURN AIR IS ABOVE | | CEILING OR DUCTED SECTION 107 FBC | | 2014 | | 4) REFER TO SECTION 312 HEATING & COOLING CALCULATIONS | | 2017 FBC (M) | | | | PLAN REVIEW BY HAROLD MOSER | | [email protected] | | OFFICE 561-805-6732 | | FAX 561-805-6676 | | |
|