Plan Review Notes For Permit 18071370 |
Permit Number |
18071370 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-08-07 08:03:33 | ****CORRECTIONS**** | | W.P.B. PERMIT: 18071370 | | REVIEWED: AUGUST 7, 2018 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC EB = FBC EXISTING BUILDING | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. PLEASE PROVIDE COPY OF THE APPROVAL LETTER FROM THE | | ASSOCIATION OR REVIEW BOARD TO STATE THAT THEY HAVE | | REVIEWED PROPOSED CHANGES TO YOUR STRUCTURE. | | | | 2. [FBC ENERGY R503.1.1.1]WHERE SOME OR ALL OF AN | | EXISTING FENESTRATION UNIT IS REPLACED WITH A NEW | | FENESTRATION PRODUCT, INCLUDING SASH AND GLAZING, THE | | REPLACEMENT FENESTRATION UNIT SHALL MEET THE APPLICABLE | | REQUIREMENTS FOR U-FACTOR AND SHGC AS PROVIDED IN TABLE | | R402.1.2. | | NEW FENESTRATION SHOULD HAVE MAXIMUM SOLAR HEAT GAIN | | CO-EFFICIENT (SHGC) OF 0.25 IN CLIMATE ZONE 1. | | | | DYLAN BATTLES | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | |
|