Plan Review Notes For Permit 18071357 |
Permit Number |
18071357 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-08-24 12:06:54 | MECHANICAL PROVISOS: | | CCOLE- 8/24/18 | | | | 1) MOTORIZED FIRE/SMOKE DAMPERS ARE REQUIRED AT THE O/A | | AND E/A DUCT PENETRATIONS OF THE FIRE-RATED MECHANICAL | | ROOM WALLS ON THE 2ND, 3RD, AND 4TH FLOORS- SHEETS | | M-102, M-103, & M-104. | | | | 2) THE KITCHEN HOOD MAKEUP AIR FAN (KSF) SHALL BE IN | | COMPLIANCE WITH SECTION 506.5.1.2 PRINTED BELOW. | | | | 506.5.1.2 IN-LINE FAN LOCATION. | | WHERE ENCLOSED DUCT SYSTEMS ARE CONNECTED TO IN-LINE | | FANS NOT LOCATED OUTDOORS, THE FAN SHALL BE LOCATED IN | | A ROOM OR SPACE HAVING THE SAME FIRE-RESISTANCE RATING | | AS THE DUCT ENCLOSURE. ACCESS SHALL BE PROVIDED FOR | | SERVICING AND CLEANING OF FAN COMPONENTS. SUCH ROOMS OR | | SPACES SHALL BE VENTILATED IN ACCORDANCE WITH THE FAN | | MANUFACTURER?S INSTALLATION INSTRUCTIONS. | | |
|