Plan Review Notes
Plan Review Notes For Permit 18071357
Permit Number 18071357
Review Stop M
Sequence Number 1
Notes
Date Text
2018-08-24 12:06:54MECHANICAL PROVISOS:
 CCOLE- 8/24/18
  
 1) MOTORIZED FIRE/SMOKE DAMPERS ARE REQUIRED AT THE O/A
 AND E/A DUCT PENETRATIONS OF THE FIRE-RATED MECHANICAL
 ROOM WALLS ON THE 2ND, 3RD, AND 4TH FLOORS- SHEETS
 M-102, M-103, & M-104.
  
 2) THE KITCHEN HOOD MAKEUP AIR FAN (KSF) SHALL BE IN
 COMPLIANCE WITH SECTION 506.5.1.2 PRINTED BELOW.
  
 506.5.1.2 IN-LINE FAN LOCATION.
 WHERE ENCLOSED DUCT SYSTEMS ARE CONNECTED TO IN-LINE
 FANS NOT LOCATED OUTDOORS, THE FAN SHALL BE LOCATED IN
 A ROOM OR SPACE HAVING THE SAME FIRE-RESISTANCE RATING
 AS THE DUCT ENCLOSURE. ACCESS SHALL BE PROVIDED FOR
 SERVICING AND CLEANING OF FAN COMPONENTS. SUCH ROOMS OR
 SPACES SHALL BE VENTILATED IN ACCORDANCE WITH THE FAN
 MANUFACTURER?S INSTALLATION INSTRUCTIONS.
  