2018-08-02 14:33:52 | 08/02/18 MET WITH MIKE. HE SUBMITTED REVISED ELEVATION |
| CERTIFICATES AND PROVISO PRODUCT APPROVALS. JG. |
| |
| |
| RESIDENTIAL (R3) ELEVATION CERTIFICATE AND PRODUCT |
| APPROVALS SUBMITTAL SECOND BUILDING REVIEW CHECKLIST. |
| CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS. |
| |
| ORIGINAL COMMENT: |
| 1- PERMIT WAS ISSUED BASED ON PLANS SHOWING THE FINISH |
| FLOOR ELEVATION OF 8'-6" FOR THE MAIN HOUSE, 7'-6" FOR |
| THE GARAGE, 8'-0" FOR THE CABANA AND 7'-6" FOR ALL |
| EQUIPMENT. FINAL ELEVATION CERTIFICATE SIGNED AND |
| SEALED BY THE SURVEYOR ON 6/6/18 SHOWS MAIN HOUSE |
| FINISH FLOOR AT 7.4 FEET, GARAGE FINISH FLOOR ELEVATION |
| AT 6.4 FEET. FINAL FINISH FLOOR ELEVATIONS DON'T MATCH |
| APPROVED PLANS AND DON'T COMPLY WITH THE CITY FLOOD |
| MANAGEMENT ORDINANCE AT THE TIME OF PERMIT ISSUANCE |
| (SEC. 94-546). |
| |
| RESPONSE: |
| PARTIALLY COMPLIED. FINAL SURVEY AND ELEVATION |
| CERTIFICATES WERE REVISED. ARCHITECT OF RECORD ALSO |
| NEEDS TO REVISE PLANS TO REFLECT THE NEW FINISH FLOOR |
| ELEVATION FOR MAIN HOUSE, GARAGE CABANA AND ALL |
| EQUIPMENT. NOTE: COORDINATE WITH ELEVATION CERTIFICATES |
| TO AVOID CONFLICTS/DELAYS. ALSO, COORDINATE WITH ITEM |
| #2 BELOW. |
| |
| |
| ORIGINAL COMMENT: |
| 2- THERE WERE NO REVISIONS SUBMITTED INDICATING THAT |
| THE FINISH FLOOR ELEVATIONS WERE CHANGED. THE FLOOD |
| INSURANCE RATE MAP (FIRM) DATED 03/01/1979 IDENTIFIES |
| THIS PROPERTY TO BE IN FLOOD ZONE A5 WITH A BASE FLOOD |
| ELEVATION OF 7 FEET USING THE 1929 NGVD ELEVATION |
| DATUM. CITY ORDINANCE REQUIRED THE FINISHED FLOOR |
| ELEVATION TO BE RAISED 6" ABOVE THE BASED FLOOD |
| ELEVATION. THIS HOUSE DOESN'T'T COMPLY WITH THE CITY |
| FLOOD MANAGEMENT SEC. 94-546. PLANS NEED TO BE REVISED |
| BY THE ARCHITECT OF RECORD. THE MAIN HOUSE FINISH FLOOR |
| NEEDS TO BE RAISED AT LEAST 6 INCHES ABOVE BASED FLOOR |
| ELEVATION (7'-6" MIN. TOTAL) AND THE GARAGE FINISH |
| FLOOR NEED TO HAVE FLOOD VENTS SHOWING COMPLIANCE WITH |
| SEC. R322.2.2 FBC-RESIDENTIAL, 5TH EDITION (2014). |
| NOTE: PRODUCT APPROVALS ARE REQUIRED FOR FLOOD VENTS. |
| |
| RESPONSE: |
| REPEAT COMMENT. PLANS WERE NOT REVISED AND SINCE GARAGE |
| FINISHED FLOOR ELEVATION IS BELOW THE BASED FLOOD |
| ELEVATION NEED TO PROVIDE COMPLETE INFORMATION FOR THE |
| FLOOD VENTS. PROVIDE PLANS /SPECIFICATIONS SHOWING THE |
| FLOOD VENTS AND PROVIDE PRODUCT APPROVAL FOR FLOOD |
| VENTS. NEED REVISED PLANS SHOWING COMPLIANCE WITH ALL |
| THE REQUIREMENTS OF SEC. R322.2.2 FBC-RESIDENTIAL. |
| NOTE: PRODUCT APPROVALS TO BE REVIEWED BY THE ARCHITECT |
| OF RECORD PRIOR TO SUBMITTAL. |
| |
| ORIGINAL COMMENT: |
| 3- THE GARAGE IS A SEPARATE STRUCTURE. IT IS NOT |
| ATTACHED TO THE HOUSE. THERE ARE THREE STRUCTURES IN |
| THIS PROPERTY: MAIN HOUSE, GARAGE AND CABANA. PROVIDE |
| ELEVATION CERTIFICATE WITH COMPLETE INFORMATION FOR |
| EACH STRUCTURE INCLUDING THE FINISH FLOOR ELEVATION OF |
| ALL EQUIPMENT. SEC. R322.1 AND SEC. R322.1.6 |
| FBC-RESIDENTIAL. |
| |
| RESPONSE: |
| SEMI COMPLIED. ELEVATION CERTIFICATE FOR EACH STRUCTURE |
| WAS PROVIDED. NEED TO REVISE THE FOLLOWING: |
| (1) THE GARAGE FINISH FLOOR ELEVATION IS BELOW THE |
| BASED FLOOD ELEVATION. THEREFORE, NEED TO PROVIDE FLOOD |
| VENTS ON DIFFERENT WALLS. NEED REVISED PLANS SHOWING |
| COMPLIANCE WITH ALL THE REQUIREMENTS OF SEC. R322.2.2 |
| FBC-RESIDENTIAL. NOTE: ELEVATION CERTIFICATE NEED TO BE |
| REVISED ONCE THE FLOOD VENTS ARE INSTALLED. |
| (2) SURVEYOR TO CLARIFY WHY THE LATITUDE AND LONGITUDE |
| IS THE SAME FOR ALL THREE STRUCTURES IF THEY ARE |
| SEPARATED. |
| (3) PROVIDE THE CORRECT BASE FLOOD ELEVATION FOR EACH |
| STRUCTURE. NOTE: ONLY THE GARAGE IS LOCATED BETWEEN |
| ELEVATION 6 AND 7. THE OTHER STRUCTURES ARE LOCATED IN |
| ELEVATION 7 OR 8 RESPECTIVELY. REVISE AS REQUIRED. |
| (4) PROVIDE CORRECT INFORMATION IN ITEM #A4: NOT ALL OF |
| THEM ARE RESIDENTIAL. CLEARLY IDENTIFY EACH STRUCTURE |
| TO AVOID CONFLICTS/DELAYS. FOR EXAMPLE: RESIDENTIAL- |
| MAIN HOUSE, RESIDENTIAL-GARAGE AND RESIDENTIAL-CABANA. |
| THIS INFORMATION WAS WRITTEN UNDER THE OWNER?S NAME. |
| WHICH IS NOT THE CORRECT PLACE FOR THIS INFORMATION. |
| REVISE AS REQUIRED AND CHANGE THE NAME OF KITCHEN FOR |
| CABANA AS SHOWN ON ARCHITECTURAL PLANS TO AVOID |
| CONFLICTS/DELAYS. |
| |
| ORIGINAL COMMENT: |
| 4- SECTION B OF THE ELEVATION CERTIFICATE NEEDS TO BE |
| FILLED ON THE BASIS OF THE FLOOD INSURANCE RATE MAP |
| (FIRM) IN EFFECT AT THE TIME OF CERTIFICATION. REVISE |
| AS REQUIRED. NOTE: PROVIDE CONVERSION FROM NGVD 1929 TO |
| NAVD 1988 WHICH IS THE CURRENT ELEVATION DATUM TO BE |
| USED. SEE FEMA ELEVATION CERTIFICATE AND INSTRUCTIONS |
| 2015 EDITION FOR COMPLETE INFORMATION REGARDING |
| ELEVATION CERTIFICATES. |
| |
| RESPONSE: |
| SEMI COMPLIED. SURVEYOR NEEDS TO PROVIDE THE CONVERSION |
| NUMBERS OF THE ELEVATIONS FROM NGVD 1929 TO NAVD 1988. |
| THIS INFORMATION IS PROVIDED IN THE COMMENTS OF SECTION |
| D. |
| |
| ORIGINAL COMMENT: |
| 5- PROVIDE FINAL SURVEY AFTER HOUSE FINISH FLOOR IS |
| RAISED AND FLOOD VENTS ARE INSTALLED. SEC. R322.1.10 |
| FBC-RESIDENTIAL. ALSO, SHOW THE BUILDING HEIGHT FOR |
| ZONING COMPLIANCE. |
| |
| RESPONSE: |
| SEMI-COMPLIED. SURVEY DOESN?T SHOW THE FINISH FLOOR |
| ELEVATION OF THE CABANA AND ALL THE EQUIPMENT. |
| |
| 6-- SURVEYOR'S RESPONSE LETTER ADDRESSING EACH COMMENT |
| WILL HELP EXPEDITE THE REVIEW PROCESS. |
| |
| |
| |
| THE FOLLOWING ARE THE COMMENTS FOR ITEMS PENDING ON |
| PROVISO DATED 06/07/18 FOR REVISION #16110786: |
| |
| 1- FLAT ROOF FLORIDA PRODUCT APPROVAL FL5680-R5 |
| SUBMITTED: PROVIDE SIGNED AND SEALED RAS 117 |
| CALCULATIONS FOR SELECTED ASSEMBLY W-55 AS REQUIRED BY |
| NOTE #8 ON PAGE 2 OF 76. |
| RESPONSE: |
| THIS INFORMATION WAS NEVER SUBMITTED. |
| |
| 2- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY |
| FAC 61G20-3.002(33) FOR: |
| A)ENTRY DOOR AS SPECIFIED ON PLANS. |
| RESPONSE: |
| MIKE SWAN SUBMITTED PRODUCT APPROVAL WITH THE INITIALS |
| OF Y.G. DATED 01/26/18. THESE ARE NOT MY INITIALS. THIS |
| PRODUCT WAS NOT APPROVED BY ME. IF THE INTENTION IS TO |
| APPLY FOR LOCAL PRODUCT APPROVAL, THEN NEED TO PROVIDE |
| COMPLETE ENGINEERING ANALYSIS WITH ENGINEER?S ORIGINAL |
| SEAL AND SIGNATURES AS REQUIRED BY CHAPTER 471 F.S. |
| (NOTE: SOME PAGES ARE NOT LEGIBLE). ALSO, THE DESIGN |
| PRESSURES AND BUILDING EXPOSURE WERE CROSSED OUT AND |
| REVISED BY HAND (NOT BY THE ENGINEER OF RECORD FOR THE |
| DOOR). |
| |
| B) EXTERIOR DOORS: FRENCH DOORS WITH SIDELITES, GARAGE |
| SWING DOOR, LAUNDRY ROOM, CABANA BATHROOM AND CABANA |
| STORAGE. |
| RESPONSE: |
| MIKE SWAN SUBMITTED COPY OF DRAWINGS FOR FLORIDA |
| PRODUCT APPROVAL FL165-R1. ACCORDING TO CITY RECORDS ON |
| FILE THIS PRODUCT APPROVAL WAS ALREADY APPROVED BY ME |
| (ALTHOUGH THE COPY SUBMITTED IS NOT THE ONE WITH THE |
| CITY STAMP). CLARIFY WHERE ARE THESE DOORS GOING TO BE |
| INSTALLED TO VERIFY WHICH OF THE ABOVE LISTED DOORS ARE |
| MISSING. |
| |
| 4- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT |
| APPROVALS. |
| |
| |
| IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT |
| JULIO GOMEZ |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| DEVELOPMENT SERVICES DEPARTMENT |
| BUILDING DIVISION |
| (561)805-6712 |
| [email protected] |
| |