Plan Review Notes
Plan Review Notes For Permit 18071291
Permit Number 18071291
Review Stop B
Sequence Number 1
Notes
Date Text
2018-08-02 10:37:26****CORRECTIONS****
 W.P.B. PERMIT: 18051306
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. [FBC 107.2.1.2]PROVIDE PRODUCT APPROVAL FOR MULL BAR
 BETWEEN WINDOW OPENENING 1&6.
  
 2. [FBC R310.2.5]MARK WINDOWS THAT PROVIDE EGRESS FOR
 EACH BEDROOM.
  
 3. [FBC ENERGY R503.1.1.1]WHERE SOME OR ALL OF AN
 EXISTING FENESTRATION UNIT IS REPLACED WITH A NEW
 FENESTRATION PRODUCT, INCLUDING SASH AND GLAZING, THE
 REPLACEMENT FENESTRATION UNIT SHALL MEET THE APPLICABLE
 REQUIREMENTS FOR U-FACTOR AND SHGC AS PROVIDED IN TABLE
 R402.1.2.
 YOUR WINDOWS SHOULD HAVE U-FACTOR OF 0.75 AND SHGC OF
 0.25
  
 NOTE:
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS".
  