Plan Review Notes For Permit 18071291 |
Permit Number |
18071291 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-08-02 10:37:26 | ****CORRECTIONS**** | | W.P.B. PERMIT: 18051306 | | | | DYLAN BATTLES | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6718 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | | | 1. [FBC 107.2.1.2]PROVIDE PRODUCT APPROVAL FOR MULL BAR | | BETWEEN WINDOW OPENENING 1&6. | | | | 2. [FBC R310.2.5]MARK WINDOWS THAT PROVIDE EGRESS FOR | | EACH BEDROOM. | | | | 3. [FBC ENERGY R503.1.1.1]WHERE SOME OR ALL OF AN | | EXISTING FENESTRATION UNIT IS REPLACED WITH A NEW | | FENESTRATION PRODUCT, INCLUDING SASH AND GLAZING, THE | | REPLACEMENT FENESTRATION UNIT SHALL MEET THE APPLICABLE | | REQUIREMENTS FOR U-FACTOR AND SHGC AS PROVIDED IN TABLE | | R402.1.2. | | YOUR WINDOWS SHOULD HAVE U-FACTOR OF 0.75 AND SHGC OF | | 0.25 | | | | NOTE: | | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW | | OF MATERIALS REQUESTED. | | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS | | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | OR "OLD SHEETS". | | |
|