Plan Review Notes For Permit 18071270 |
Permit Number |
18071270 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-07-31 14:26:15 | PERMIT # 18071270 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | SUBMITTAL APPROVED PROVISO. THE FOLLOWING ITEMS SHALL | | BE COMPLIED WITH AND VERIFIED IN THE FIELD BY THE FIRE | | INSPECTOR. | | | | 1) FLOORS 2 - 6 HAVE NO DIVIDING FIRE SEPERATION AND | | CANNOT BE SPLIT. THE FIRE SPRINKLER SYSTEM FOR ALL OF | | FLOORS 2-6 SHALL BE INSTALLED, TESTED, INSPECTED AND | | APPROVED PRIOR TO BEING USED FOR STORAGE AND/OR | | PARKING. | | PER THE FIRE INSPECTOR, THIS AREA HAD SOME PAINTED FIRE | | SPRINKLER HEADS THAT NEEDED TO BE REPLACED. | | | | 2) THE FIRE PUMP LOCATED IN PHASE 2/3 HAS NOT YET BEEN | | INSPECTED, TESTED, AND APPROVED. | | | | 3) ALL REQUIRED FIRE AND LIFE SAFETY SYSTEMS THAT ARE | | REQUIRED FOR THE SPECIFIC OCCUPANCY TYPES ADDRESSED BY | | THE PHASES, SHALL BE INSTALLED, INSPECTED, TESTED, AND | | APPROVED, PRIOR TO OCCUPANCY. | | I.E. PHASE 2, STORAGE OCCUPANCY OF FLOORS 2-6. | | | | 4) TCO OF THE PHASES WILL BE DEPENDENT ON INSPECTION | | AND APPROVAL BY THIS OFFICE. | | | | SUE ELLEN CALDERON | | ASSISTANT FIRE MARSHAL | | [email protected] | | |
|