2018-07-31 14:26:15PERMIT # 18071270
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 SUBMITTAL APPROVED PROVISO. THE FOLLOWING ITEMS SHALL
 BE COMPLIED WITH AND VERIFIED IN THE FIELD BY THE FIRE
 INSPECTOR.
  
 1) FLOORS 2 - 6 HAVE NO DIVIDING FIRE SEPERATION AND
 CANNOT BE SPLIT. THE FIRE SPRINKLER SYSTEM FOR ALL OF
 FLOORS 2-6 SHALL BE INSTALLED, TESTED, INSPECTED AND
 APPROVED PRIOR TO BEING USED FOR STORAGE AND/OR
 PARKING.
 PER THE FIRE INSPECTOR, THIS AREA HAD SOME PAINTED FIRE
 SPRINKLER HEADS THAT NEEDED TO BE REPLACED.
  
 2) THE FIRE PUMP LOCATED IN PHASE 2/3 HAS NOT YET BEEN
 INSPECTED, TESTED, AND APPROVED.
  
 3) ALL REQUIRED FIRE AND LIFE SAFETY SYSTEMS THAT ARE
 REQUIRED FOR THE SPECIFIC OCCUPANCY TYPES ADDRESSED BY
 THE PHASES, SHALL BE INSTALLED, INSPECTED, TESTED, AND
 APPROVED, PRIOR TO OCCUPANCY.
 I.E. PHASE 2, STORAGE OCCUPANCY OF FLOORS 2-6.
  
 4) TCO OF THE PHASES WILL BE DEPENDENT ON INSPECTION
 AND APPROVAL BY THIS OFFICE.
  
 SUE ELLEN CALDERON
 ASSISTANT FIRE MARSHAL
 [email protected]
  