Plan Review Notes
Plan Review Notes For Permit 18071153
Permit Number 18071153
Review Stop P
Sequence Number 1
Notes
Date Text
2018-08-06 17:20:1408/06/2018 1ST GAS REVIEW **DENIED** WITH COMMENTS
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 1. SUBMIT TWO COPIES MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR ALL EQUIPMENT
 (FIREPLACE) TO VERIFY COMPLIANCE.
 2. SUBMIT TWO COPIES OF DETAIL SHOWING THE TYPE,
 LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE THE
 ROOF AND ANCHORING DETAILS OF THE GAS VENT FOR
 FIREPLACE.
 3. FIRE PLACE MANUFACTURES INSTALLATION INSTRUCTION
 SHALL BE ON SITE AT TIME OF INSTALLATION.
 4. PLANS CALL FOR A STEAM SHOWER PLEASE PROVIDE
 LOCATION AND SPECIFICATION FOR THE STEAM GENERATOR,
 PLEASE PROVIDE MANUFACTURE SPECIFICATION. IF THE STEAM
 UNIT IS UNDER A SHOWER SEAT, HOW IS THE STEAM ENTERING
 THE SHOWER? WHERE IS THE DISCHARGE OF THE UNIT GOING TO
 DUMP IN? PLEASE CLARIFY WHAT TYPE OF PROTECTION IS
 BEING USED AND SHOW WHERE IT GOING IN THE SHOWER. WPB
 AMENDMENTS TO THE FBC 107.2.1
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
 561-805-6720
  