Plan Review Notes For Permit 18071153 |
Permit Number |
18071153 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-08-06 17:20:14 | 08/06/2018 1ST GAS REVIEW **DENIED** WITH COMMENTS | | | | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS | | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE | | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. | | | | 1. SUBMIT TWO COPIES MANUFACTURER?S SPECIFICATION | | SHEETS/INSTALLATION MANUAL FOR ALL EQUIPMENT | | (FIREPLACE) TO VERIFY COMPLIANCE. | | 2. SUBMIT TWO COPIES OF DETAIL SHOWING THE TYPE, | | LOCATION, SIZE, TERMINATION POINT, HEIGHT ABOVE THE | | ROOF AND ANCHORING DETAILS OF THE GAS VENT FOR | | FIREPLACE. | | 3. FIRE PLACE MANUFACTURES INSTALLATION INSTRUCTION | | SHALL BE ON SITE AT TIME OF INSTALLATION. | | 4. PLANS CALL FOR A STEAM SHOWER PLEASE PROVIDE | | LOCATION AND SPECIFICATION FOR THE STEAM GENERATOR, | | PLEASE PROVIDE MANUFACTURE SPECIFICATION. IF THE STEAM | | UNIT IS UNDER A SHOWER SEAT, HOW IS THE STEAM ENTERING | | THE SHOWER? WHERE IS THE DISCHARGE OF THE UNIT GOING TO | | DUMP IN? PLEASE CLARIFY WHAT TYPE OF PROTECTION IS | | BEING USED AND SHOW WHERE IT GOING IN THE SHOWER. WPB | | AMENDMENTS TO THE FBC 107.2.1 | | | | LUIS A. CRESPO | | PLUMBING INSPECTOR / | | PLUMBING PLAN REVIEW | | AVAILABLE FROM 1:00 PM TO 4:00 PM | | [email protected] | | 561-805-6720 | | |
|