2018-08-22 11:23:36 | 1ST REVIEW: |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| PLUMBING COMMENTS: |
| |
| 1. THE 3 COMPARTMENT SINK SHALL HAVE HOT WATER NOT |
| TEMPERED WATER AS REQUIRED FOR THE PUBLIC HAND WASHING |
| LAVATORY'S. IT APPEARS THAT YOU HAVE IT CONNECTED TO |
| THE 110 DEG. WATER LINE WHICH IS TEMPERED IT SHOULD BE |
| CONNECTED TO THE 140 DEG. PER FBC PL 607.1 |
| |
| 2. PLACE NOTE ON PLAN A SEPARATE PERMIT IS REQUIRED FOR |
| THE GREASE INTERCEPTOR. WPB AMEND TO FBC 107.2.1 |
| |
| 3. PROVIDE SIZING CALCULATION FROM SCHIER FOR GREASE |
| INTERCEPTOR THIS WAS A COMMENT FROM THE FIRST ROUND OF |
| COMMENTS ON THE ORIGINAL PLANS THAT WAS NEVER COMPLIED |
| WITH. WPB AMEND TO FBC 107.2.1 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |