2018-08-22 11:23:361ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE 3 COMPARTMENT SINK SHALL HAVE HOT WATER NOT
 TEMPERED WATER AS REQUIRED FOR THE PUBLIC HAND WASHING
 LAVATORY'S. IT APPEARS THAT YOU HAVE IT CONNECTED TO
 THE 110 DEG. WATER LINE WHICH IS TEMPERED IT SHOULD BE
 CONNECTED TO THE 140 DEG. PER FBC PL 607.1
  
 2. PLACE NOTE ON PLAN A SEPARATE PERMIT IS REQUIRED FOR
 THE GREASE INTERCEPTOR. WPB AMEND TO FBC 107.2.1
  
 3. PROVIDE SIZING CALCULATION FROM SCHIER FOR GREASE
 INTERCEPTOR THIS WAS A COMMENT FROM THE FIRST ROUND OF
 COMMENTS ON THE ORIGINAL PLANS THAT WAS NEVER COMPLIED
 WITH. WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  