2018-08-14 08:19:131ST REVIEW FBC-2017 MECHANICAL
 PERMIT #18071140
 8/14/18
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE REVISED AC SIZING CALCULATIONS FOR RTU #2
 INDICATE AN 8-TON SYSTEM IS REQUIRED, HOWEVER THE
 CALCULATIONS SUBMITTED UNDER THE HOOD PERMIT #17110388
 INDICATE A 10-TON SYSTEM IS REQUIRED- PLEASE CORRECT.
  
 2) SHEET M0.1: THE EXHAUST FAN AND SUPPLY FAN CFMS
 SHOWN IN THE O/A BALANCE DIAGRAM DO NOT MATCH THE CFM
 CAPACITIES SHOWN ON THE HOOD PLAN- PLEASE CORRECT.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  