Plan Review Notes
Plan Review Notes For Permit 18071140
Permit Number 18071140
Review Stop E
Sequence Number 1
Notes
Date Text
2018-08-13 09:44:20CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ONLY ONE SERVICE IS PERMITTED. REVISED PLAN SHOWS
 TWO SEPARATE DROPS AND SERVICES TO THE SAME OCCUPANCY.
 PROVIDE CORRECTION. NEC 230.2
 2. FOR THE GENERATOR FEED, A DISCONNECT AND EMERGENCY
 STOP BUTTON IS ALSO REQUIRED AT THE BUILDING SERVED.
 PROVIDE CORRECTION. NEC 225.32
 3. PROVIDE BLOCK NOTE THAT THE GENERATOR REQUIRES
 SEPARATE PERMIT AND PLAN SUBMITTAL. WPB FBC 105.1
 4. VALUE FOR WORK STATED ON REVISION APPLICATION
 APPEARS LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE
 AND VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR.
 FBC 109.3
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  