2018-08-13 09:44:20 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. ONLY ONE SERVICE IS PERMITTED. REVISED PLAN SHOWS |
| TWO SEPARATE DROPS AND SERVICES TO THE SAME OCCUPANCY. |
| PROVIDE CORRECTION. NEC 230.2 |
| 2. FOR THE GENERATOR FEED, A DISCONNECT AND EMERGENCY |
| STOP BUTTON IS ALSO REQUIRED AT THE BUILDING SERVED. |
| PROVIDE CORRECTION. NEC 225.32 |
| 3. PROVIDE BLOCK NOTE THAT THE GENERATOR REQUIRES |
| SEPARATE PERMIT AND PLAN SUBMITTAL. WPB FBC 105.1 |
| 4. VALUE FOR WORK STATED ON REVISION APPLICATION |
| APPEARS LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE |
| AND VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. |
| FBC 109.3 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD |
| SHEETS?. |
| |