Plan Review Notes
Plan Review Notes For Permit 18071126
Permit Number 18071126
Review Stop M
Sequence Number 2
Notes
Date Text
2018-10-22 13:01:382ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18071126
 10/22/18
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEM- SECTION C403.2.1 FBC-17 ENERGY CONSERVATION.
  
 2) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE
 DINING AND BAR ROOMS- TABLE 403.3.1 FBC-17 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR.
  
 3) PROVIDE AN AIR DEVICE SCHEDULE AND INDICATE THE
 SUPPLY CFMS AT EACH DIFFUSER ON THE PLAN. SHOW THE
 LOCATION OF THE MAIN RETURN GRILL AND PROVIDE
 DIMENSIONS- SECTION 603.1 FBC M.
  
 4) PROVIDE A CONDENSATE DISPOSAL PLAN- SECTION 307 FBC
 M. SHOW THE TYPE OF PRIMARY PIPING, THE PIPING RUN AND
 DISCHARGE LOCATION.
  
 5) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE
 NEW CONDENSER- SECTION 301.15
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  