2018-10-22 13:01:38 | 2ND REVIEW FBC-2017 MECHANICAL |
| PERMIT #18071126 |
| 10/22/18 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| AC SYSTEM- SECTION C403.2.1 FBC-17 ENERGY CONSERVATION. |
| |
| 2) PROVIDE MINIMUM VENTILATION CALCULATIONS FOR THE |
| DINING AND BAR ROOMS- TABLE 403.3.1 FBC-17 MECHANICAL. |
| PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND |
| PROVIDED CFMS OF OUTDOOR AIR. |
| |
| 3) PROVIDE AN AIR DEVICE SCHEDULE AND INDICATE THE |
| SUPPLY CFMS AT EACH DIFFUSER ON THE PLAN. SHOW THE |
| LOCATION OF THE MAIN RETURN GRILL AND PROVIDE |
| DIMENSIONS- SECTION 603.1 FBC M. |
| |
| 4) PROVIDE A CONDENSATE DISPOSAL PLAN- SECTION 307 FBC |
| M. SHOW THE TYPE OF PRIMARY PIPING, THE PIPING RUN AND |
| DISCHARGE LOCATION. |
| |
| 5) PROVIDE WIND LOAD ENGINEERING FOR TIE DOWN OF THE |
| NEW CONDENSER- SECTION 301.15 |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS |
| |