Plan Review Notes
Plan Review Notes For Permit 18071126
Permit Number 18071126
Review Stop B
Sequence Number 1
Notes
Date Text
2018-08-25 19:10:30****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. A1A STATES THAT THE EXISTING PARKING LOT IS TO
 REMAIN. SEE FBC A 202.1, 202.4, PATH OF TRAVEL IS TO BE
 ACCESSIBLE. A2 DOES NOT SHOW ANY ACCESSIBLE SPACES; A1A
 DOES NOT SHOW AN ACCESS AISLE FOR THE "EXISTING
 HANDICAP PARKING SPACE". AERIALS APPEAR TO SHOW NO
 STRIPING. THERE IS NO RECORD OF A PAVING OR RESTRIPE
 PERMIT.
  
 ALSO PLEASE CONFIRM THAT THE "EXISTING RAMP" COMPLIES
 WITH FBC ACCESSIBILITY AS I WAS UNABLE TO FIND A PERMIT
 FOR THIS WORK. IF IT COMPLIES, PLEASE NOTE THAT YOU
 HAVE CONFIRMED COMPLIANCE ON THE PLAN. IF IT DOES NOT
 COMPLY, PLEASE REVISE PLAN.
  
 SEE ALSO PLUMBING COMMENTS.
  
 2. A5, SOME NOTES ARE TOO SMALL TO READ, REVISE, FBC
 107.
  
 3. FBC B 1004, REVISE PLAN TO INCLUDE OCCUPANCY
 CLASSIFICATION AND OCCUPANT LOAD.
  
 4. FBC B 107, IF THIS IS A2 WITH AN OCCUPANT LOAD OVER
 50, PANIC BARS REQUIRED. IF REQUIRED, INDICATE THIS
 OPTION ON THE DOOR PRODUCT APPROVAL.
  
 5. ON THE DOOR PRODUCT APPROVAL, INDICATE WHICH
 THRESHOLD OPTION IS SELECTED TO SHOW COMPLIANCE WITH
 FBC A 303.
  
 6. FIXED GLASS PRODUCT APPROVALS AND ROOF PRODUCT
 APPROVALS WERE NOT SUBMITTED. DO YOU WANT FOR THIS TO
 BE DEFFERED? FBC 107.
  
 7. THIS PROPERTY HAS TWO EXPIRED PERMITS, PLEASE
 ADDRESS, FBC 107.
  
 8. FBC 107, PRODUCT APPROVALS TO BE REVIEWED BY
 DESIGNER OF RECORD.
  
  
  
  
  
  
  