2018-08-25 19:10:30 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| FBC R = FBC RESIDENTIAL |
| |
| 1. A1A STATES THAT THE EXISTING PARKING LOT IS TO |
| REMAIN. SEE FBC A 202.1, 202.4, PATH OF TRAVEL IS TO BE |
| ACCESSIBLE. A2 DOES NOT SHOW ANY ACCESSIBLE SPACES; A1A |
| DOES NOT SHOW AN ACCESS AISLE FOR THE "EXISTING |
| HANDICAP PARKING SPACE". AERIALS APPEAR TO SHOW NO |
| STRIPING. THERE IS NO RECORD OF A PAVING OR RESTRIPE |
| PERMIT. |
| |
| ALSO PLEASE CONFIRM THAT THE "EXISTING RAMP" COMPLIES |
| WITH FBC ACCESSIBILITY AS I WAS UNABLE TO FIND A PERMIT |
| FOR THIS WORK. IF IT COMPLIES, PLEASE NOTE THAT YOU |
| HAVE CONFIRMED COMPLIANCE ON THE PLAN. IF IT DOES NOT |
| COMPLY, PLEASE REVISE PLAN. |
| |
| SEE ALSO PLUMBING COMMENTS. |
| |
| 2. A5, SOME NOTES ARE TOO SMALL TO READ, REVISE, FBC |
| 107. |
| |
| 3. FBC B 1004, REVISE PLAN TO INCLUDE OCCUPANCY |
| CLASSIFICATION AND OCCUPANT LOAD. |
| |
| 4. FBC B 107, IF THIS IS A2 WITH AN OCCUPANT LOAD OVER |
| 50, PANIC BARS REQUIRED. IF REQUIRED, INDICATE THIS |
| OPTION ON THE DOOR PRODUCT APPROVAL. |
| |
| 5. ON THE DOOR PRODUCT APPROVAL, INDICATE WHICH |
| THRESHOLD OPTION IS SELECTED TO SHOW COMPLIANCE WITH |
| FBC A 303. |
| |
| 6. FIXED GLASS PRODUCT APPROVALS AND ROOF PRODUCT |
| APPROVALS WERE NOT SUBMITTED. DO YOU WANT FOR THIS TO |
| BE DEFFERED? FBC 107. |
| |
| 7. THIS PROPERTY HAS TWO EXPIRED PERMITS, PLEASE |
| ADDRESS, FBC 107. |
| |
| 8. FBC 107, PRODUCT APPROVALS TO BE REVIEWED BY |
| DESIGNER OF RECORD. |
| |
| |
| |
| |
| |
| |
| |