Plan Review Notes For Permit 18071081 |
Permit Number |
18071081 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2018-09-06 17:20:11 | FLORIDA BUILDING CODE 2017 6TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED | | NFPA 70 2014 EDITION | | | | JAKE LEAHY | | ELECTRICAL PLANS EXAMINER II | | 561-805-6713 | | [email protected] | | | | PLANS STILL SHOW 1200 AMPERE SWITCH, NEED TO SHOW THAT | | IT IS ONLY 1200 WITH A 1000A TRIPPING MODUAL SO WIRE | | MATCHES MAIN. | | | | HOW DOES THE KIRK KEY SYSTEM WORK ON A TAP BOX? | | | | ONE METER BEING BLANKED OFF MAIN MISSING FROM THAT | | METER. | | | | SUBMIT CUT SHEETS FOR KIRK KEY SYSTEM | | | | |
|