2018-09-06 17:20:11FLORIDA BUILDING CODE 2017 6TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 6TH ED
 NFPA 70 2014 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PLANS STILL SHOW 1200 AMPERE SWITCH, NEED TO SHOW THAT
 IT IS ONLY 1200 WITH A 1000A TRIPPING MODUAL SO WIRE
 MATCHES MAIN.
  
 HOW DOES THE KIRK KEY SYSTEM WORK ON A TAP BOX?
  
 ONE METER BEING BLANKED OFF MAIN MISSING FROM THAT
 METER.
  
 SUBMIT CUT SHEETS FOR KIRK KEY SYSTEM
  
  