Plan Review Notes
Plan Review Notes For Permit 18070967
Permit Number 18070967
Review Stop E
Sequence Number 2
Notes
Date Text
2018-08-27 07:08:01ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. LOW VOLTAGE AND HIGH VOLTAGE STILL TOGETHER IN J-BOX
 WITHOUT SEPARATION. CANNOT MIX LOW VOLTAGE AND HIGH
 VOLTAGE. 725.136B NEC
  
 2. NO PREVIOUS/CLOSED OR CURRENT/OPEN ELECTRICAL PERMIT
 FOR 1751 PBL BLVD E243. DISCONNECT SWITCH AND TIME
 CLOCK ARE NOT EXISTING. LICENSED ELECTRICIAN REQUIRED
 FOR INSTALLATION. HOLD ON PERMIT UNTIL LICENSED
 ELECTRICAL CONTRACTOR APPLIES FOR SUB PERMIT.
  
 3. DISCONNECT WITHIN SIGHT OF SIGN HAS BEEN REMOVED
 FROM PLAN, WAS ON PREVIOUS PLAN?? 600.6A1 NEC
  
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER