2018-08-27 07:08:01 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. LOW VOLTAGE AND HIGH VOLTAGE STILL TOGETHER IN J-BOX |
| WITHOUT SEPARATION. CANNOT MIX LOW VOLTAGE AND HIGH |
| VOLTAGE. 725.136B NEC |
| |
| 2. NO PREVIOUS/CLOSED OR CURRENT/OPEN ELECTRICAL PERMIT |
| FOR 1751 PBL BLVD E243. DISCONNECT SWITCH AND TIME |
| CLOCK ARE NOT EXISTING. LICENSED ELECTRICIAN REQUIRED |
| FOR INSTALLATION. HOLD ON PERMIT UNTIL LICENSED |
| ELECTRICAL CONTRACTOR APPLIES FOR SUB PERMIT. |
| |
| 3. DISCONNECT WITHIN SIGHT OF SIGN HAS BEEN REMOVED |
| FROM PLAN, WAS ON PREVIOUS PLAN?? 600.6A1 NEC |
| |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |