Plan Review Notes
Plan Review Notes For Permit 18070967
Permit Number 18070967
Review Stop E
Sequence Number 1
Notes
Date Text
2018-07-30 06:41:42ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. J-BOX WITH 120V HAS LINE AND LOAD END OF POWER
 SUPPLY IN IT ALSO. CANNOT MIX HIGH AND LOW VOLTAGE.
 725.136B NEC
  
 2. IN RESPONSE TO COMMENT THAT "TIMECLOCK IS EXISTING".
 TIMECLOCK MUST STILL CONFORM TO FBC CE 405.2.4. TIME
 CLOCK MUST BE ASTRONOMICAL WITH 10/HOUR BATTERY BACK
 UP.
  
 3. NOT ALL PAGES OF PLAN ARE SIGNED/SEALED BY ENGINEER.
 ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND
 SIGNED/SEALED BY A DESIGN PROFESSIONAL OR THE
 ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS
 471.003(2)(H); 471.025; WPB FBC 107.1
  
 4. UNABLE TO ISSUE ELECTRICAL SUB-PERMIT TO ES LICENSE.
 NEED LICENSED ELECTRICIAN TO INSTALL REQUIRED TIMECLOCK
 AND 120V DISCONNECT FOR SIGN. THIS WORK IS OUT OF SCOPE
 FOR AN ES LICENSE. PLEASE SEE SCOPE OF ES LICENSE
 BELOW;
  
  
 SIGN CONTRACTORS F.S. 489.505 (#19) AND F.A.C.
 61G6-7.001 SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN
 SPECIALTY CONTRACTOR)
  
 THE SCOPE OF CERTIFICATION INCLUDES THE STRUCTURAL
 FABRICATION INCLUDING CONCRETE FOUNDATION, ERECTION,
 INSTALLATION, ALTERATION, REPAIR, SERVICE AND WIRING OF
 ELECTRICAL SIGNS AND OUTLINE LIGHTING. THE SCOPE OF
 CERTIFICATION SHALL NOT INCLUDE THE PROVISION OF, OR
 ANY ELECTRICAL WORK BEYOND, THE LAST DISCONNECT MEAN OR
 TERMINAL POINTS. HOWEVER, A CONTRACTOR CERTIFIED UNDER
 THIS SECTION MAY PROVIDE THE ELECTRICAL ENTRANCE
 REQUIREMENTS FOR METERING AND MAIN DISCONNECT OF REMOTE
 BILLBOARDS OR SIGNS WHICH ARE INDEPENDENT OF ANY
 STRUCTURE OR BUILDING AND WHICH REQUIRE NO MORE THAN
 TWENTY-FIVE (25) KILOWATTS AT TWO HUNDRED FIFTY (250)
 VOLTS MAXIMUM.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved