2018-07-30 06:41:42 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. J-BOX WITH 120V HAS LINE AND LOAD END OF POWER |
| SUPPLY IN IT ALSO. CANNOT MIX HIGH AND LOW VOLTAGE. |
| 725.136B NEC |
| |
| 2. IN RESPONSE TO COMMENT THAT "TIMECLOCK IS EXISTING". |
| TIMECLOCK MUST STILL CONFORM TO FBC CE 405.2.4. TIME |
| CLOCK MUST BE ASTRONOMICAL WITH 10/HOUR BATTERY BACK |
| UP. |
| |
| 3. NOT ALL PAGES OF PLAN ARE SIGNED/SEALED BY ENGINEER. |
| ELECTRICAL PLAN IS REQUIRED TO BE DESIGNED AND |
| SIGNED/SEALED BY A DESIGN PROFESSIONAL OR THE |
| ELECTRICAL CONTRACTOR QUALIFIER. PROVIDE CORRECTION. FS |
| 471.003(2)(H); 471.025; WPB FBC 107.1 |
| |
| 4. UNABLE TO ISSUE ELECTRICAL SUB-PERMIT TO ES LICENSE. |
| NEED LICENSED ELECTRICIAN TO INSTALL REQUIRED TIMECLOCK |
| AND 120V DISCONNECT FOR SIGN. THIS WORK IS OUT OF SCOPE |
| FOR AN ES LICENSE. PLEASE SEE SCOPE OF ES LICENSE |
| BELOW; |
| |
| |
| SIGN CONTRACTORS F.S. 489.505 (#19) AND F.A.C. |
| 61G6-7.001 SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN |
| SPECIALTY CONTRACTOR) |
| |
| THE SCOPE OF CERTIFICATION INCLUDES THE STRUCTURAL |
| FABRICATION INCLUDING CONCRETE FOUNDATION, ERECTION, |
| INSTALLATION, ALTERATION, REPAIR, SERVICE AND WIRING OF |
| ELECTRICAL SIGNS AND OUTLINE LIGHTING. THE SCOPE OF |
| CERTIFICATION SHALL NOT INCLUDE THE PROVISION OF, OR |
| ANY ELECTRICAL WORK BEYOND, THE LAST DISCONNECT MEAN OR |
| TERMINAL POINTS. HOWEVER, A CONTRACTOR CERTIFIED UNDER |
| THIS SECTION MAY PROVIDE THE ELECTRICAL ENTRANCE |
| REQUIREMENTS FOR METERING AND MAIN DISCONNECT OF REMOTE |
| BILLBOARDS OR SIGNS WHICH ARE INDEPENDENT OF ANY |
| STRUCTURE OR BUILDING AND WHICH REQUIRE NO MORE THAN |
| TWENTY-FIVE (25) KILOWATTS AT TWO HUNDRED FIFTY (250) |
| VOLTS MAXIMUM. |
| |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| PREVIOUSLY REVIEWED SHEETS. |
| CODES IN EFFECT: |
| |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2017 6TH ED. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |