Plan Review Notes For Permit 18070907 |
Permit Number |
18070907 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2018-07-28 06:03:48 | 1) THE VALUE OF THIS PROJECT STATED ON THE PERMIT | | APPLICATION APPEARS LOW. SUBMIT A DETAILED ESTIMATE OR | | A BONA FIDE SIGNED CONTRACT SHOWING THE FULL VALUE OF | | THIS JOB PER THE WPB AMEND. TO FBC SEC. 109.3. | | 2) THE TDH RESULTS HAVE BEEN SUBMITTED BUT NOT THE | | CALCULATIONS. SUBMIT THE TOTAL DYNAMIC HEAD | | CALCULATIONS FOR REVIEW. | | 3) SUBMIT TWO LEGIBLE COPIES OF THE POOL PUMP CURVE. | | IDENTIFY ON THE PUMP CURVE WHICH CURVE KEY IS SPECIFIC | | TO THE PUMP BEING INSTALLED ON THIS POOL. THIS IS | | NEEDED TO CONFIRM THE MAXIMUM SYSTEM FLOW FROM THE TDH | | CALCULATIONS. | | | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | |
|